6.3
Checking of magnesium anode rod
The magnesium anode rod is a sacrificial anode rod which
will be consumed during its operation.
V
Check the diameter and surface of the anode rod
annually
.
Visual inspection of the anode rod
V
If not yet done, remove the top tank cover, insulation
material and disconnect any pipe (AW and EZ).
V
Remove hex. bolts to disassemble clean-out cover [1]
and magnesium anode rod [2].
V
Check anode rod for surface irregularities and diame-
ter.
V
When the diameter is reduced to ½" (15 mm), replace
the anode rod.
V
Install the new anode rod back into the tank.
Fig. 17 Check magnesium anode rod
1
Clean-out cover
2
Magnesium anode rod
When the anode rod is not professionally and
annually maintained, the tank will loose its
warranty. Annual service records must be
maintained and shown in case of a warranty
claim along with an original proof of pur-
chase.
Avoid contact between the anode rod and oil
or grease.
V
Keep the anode rod clean.