Maintenance
Logalux PL750/2 S - Changes may be made following technical improvements!
25
6.5
Placing solar tank back in operation
after cleaning
V
Install new gasket [3] with clean-out cover [1] and
magnesium anode rod.
V
Connect ground wire to tank.
V
Tighten 6 bolts by hand.
V
Further tighten the bolts with a wrench. Tighten evenly.
Torque bolts evenly to about 18 - 22 lb-ft (25 - 30 Nm).
V
Install AW and EZ pipes to the tank connections.
V
Install DHW sensor and insertion wire [4] into dry well.
V
Fill the solar-combi tank and start up the system.
V
Check all connections and clean-out cover for leaks.
V
Install insulation piece and top tank cover.
Fig. 19 Install clean-out cover with magnesium anode
rod
1
Clean-out cover
2
Ground wire
3
Gasket clean-out cover
4
Insertion wire DHW sensor
5
Ground wire eyelet
Caution:
Tank damage due to a defective
gasket!
V
To avoid leak sites, replace the clean-out
gasket following removal of the clean-out
cover.