54
my Home - control
exAmples of configurAtion
The drawing shows a system for the management of three lamps and three
rolling shutters. Each actuator is identified by three numbers: Room number
(A), device progressive number (PL for light actuators and PL1 and PL2 for
rolling shutter actuators) and Group (G) of belonging.
The control devices are instead distinguished from the configurators in
positions A and PL which specify the addresses of the actuators receiving
the control (one only, a group or several room actuators) and from the
configurators in position M to define the function (ON/OFF or ON/DOWN).
configurAtion
Defining the addresses
Point-point control
Control 1 (A = 1, PL = 1) controls actuators 1 (A = 1, PL = 1 and G = 1). In the
same way control 2 (A = 1, PL = 2) controls actuator 2 (A = 1, PL = 2 and
G = 1) etc..
Room control
Room control 8 (A=AMB, PL=2) controls actuators 4 and 5 marked with A=2
Group control
Group control 7 marked with A=GR and PL=1, controls actuators 1 and 2
marked with G=1
General control
The devices identified A=GEN and PL= - (no configurator) send a general
control to all the actuators, for the lights and for the rolling shutters, in the
system.
NOTE: The actuators which manage the rolling shutters, unlike those for the
lights, are configured in the same way in the two positions PL1 and PL2.
control operating mode
The configurator inserted in position M of each control device identifies the
operating mode.
The O/I configurator specifies a lamp switching on control which is given by
pressing the upper key cover (ON) and the lower key cover (OFF).
The configurators and
M
in position M instead specify a control to
manage the rolling shutters intended for actuators 4, 5 and 6.
point-point control
group
control
room
control
actuators
BUS
general control
2
3
4
5
6
7
8
230V a.c.
A = 1
PL = 2
M = 0/I
A = 1
PL = 3
M = 0/I
A = 2
PL = 1
M = M
A = GEN
PL = -
M = 0/I
A = 1
PL = 1
G = 1
A = 1
PL = 2
G = 1
A = 1
PL = 3
G = 2
A = 2
PL1 = 1
PL2 = 1
A = 2
PL1 = 2
PL2 = 2
A = 3
PL1 = 1
PL2 = 1
A = AMB
PL = 2
M = M
A = GR
PL = 1
M = 0/I
A = 2
PL = 2
M = M
A = 3
PL = 1
M = M
1
2
3
4
5
6
A = GEN
PL = -
M = M
9
10
1
A = 1
PL = 1
M = 0/I
Содержание MH08CT/GB
Страница 1: ...MH08CT GB TECHNICAL GUIDE 08 Control My Home Control MH08CT GB ...
Страница 19: ...17 gENERal FEaTURES 17 MY HOME CONTROL TECHNICAL GUIDE www www Internet Hand held computer PC F453AV ...
Страница 152: ...150 MY HOME control NOTES ...
Страница 153: ...programmING 151 programmING MY HOME control technical GUIDE NOTES NOTES ...
Страница 154: ...152 MY HOME control NOTES ...
Страница 155: ...153 NOTES NOTES ...