The purpose of this control is to permit the safe shutdown
of the furnace during certain blocked vent conditions.

a. Disconnect power to furnace and remove vent connector

from furnace outlet collar. Be sure to allow time for vent
pipe to cool down before removing.

b. Set room thermostat above room temperature and restore

power to furnace.

c. After normal startup, allow furnace to operate for 2

minutes, then block flue outlet (50 percent). Furnace
should cycle off within 3 minutes.

d. Remove blockage and reconnect vent pipe to furnace

outlet collar.

e. Wait 5 minutes and then reset draft safeguard switch.

4. Check pressure switch.

This control proves operation of draft inducer blower.

a. Turn off 115-v power to furnace.

b. Remove control door and disconnect inducer motor lead

wires from wire harness.

c. Turn on 115-v power to furnace.

d. Close thermostat switch as if making normal furnace

start. If the burners do not light, the pressure switch is
functioning properly.

e. Turn off 115-v power to furnace.

f. Reconnect inducer motor wires, replace control door, and

turn on 115-v power.

5. Check auxiliary limits.

a. Turn off 115-v power to furnace.

b. Remove blower access door.

c. Disconnect red motor lead at blower speed selector.

Mark terminal for proper reconnection.

d. Replace blower access door.

e. Turn on 115-v power to furnace. Be sure room thermo-

stat is "calling for heat".

f. Allow furnace to operate until auxiliary limit activates,

but DO NOT operate furnace longer than 4 minutes.

g. If furnace operates for 4 minutes, check/replace auxiliary

limit switch.

h. Turn off 115-v power to furnace.

i. Remove blower access door.

j. Reconnect red motor lead and replace door.

k. Turn on 115-v power to furnace.

F.

Checklist

1. Put away tools and instruments, and clean up debris.

2. Verify manual reset switches have continuity.

3. Ensure blower and control access doors are properly in-

stalled.

4. Cycletest furnace with room thermostat.

5. Check operation of accessories per manufacturer’s instruc-

tions.

6. Review User’s Manual with owner.

7. Leave literature packet near furnace.

—13—

Содержание 396HAD

Страница 1: ...t up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to the pot...

Страница 2: ...rther information the National Fuel Gas Code is available from National Fire Protection Association Inc Battery march Park Quincy MA 02269 American Gas Association 1515 Wilson Boulevard Arlington VA 2...

Страница 3: ...it must be installed so that the burners and ignition source are located at least 18 in above the floor The furnace should be protected from physical damage by vehicles When a furnace is installed in...

Страница 4: ...t opening directly communicating with the outdoors should be provided This opening should have a minimum free area of 1 sq in per 5000 Btuh of total input rating for all equipment in the enclosure If...

Страница 5: ...nnected to the furnace install the filters in a V formation inside the return air plenum See Fig 7 V GAS PIPING Gas piping must be installed in accordance with national and local codes Refer to the cu...

Страница 6: ...hin 72 in of the furnace A 1 8 in NPT plugged tapping accessible for test gage connection must be installed immediately upstream of the gas supply connection to the furnace and downstream of the manua...

Страница 7: ...link FL and limit switch LS to energize R With the furnace pilot lit the thermocouple will energize the thermal magnet circuit of gas valve GV permitting gas flow to the remaining portion of the gas...

Страница 8: ...h lighting operating instructions on the furnace The pilot flame should be soft blue in color and surround 3 8 in to 1 2 in of the thermocouple element tip The flame must never come in contact with an...

Страница 9: ...IVE BLADE TYPE FUSE FIELD INSTALLED FUSIBLE LINK GAS VALVE REDUNDANT HEATING FAN RELAY SPST N O INDUCED DRAFT MOTOR INDUCER DRAFT RELAY DPST N O BLOWER DOOR INTERLOCK SWITCH SPST N O JUNCTION BOX LIMI...

Страница 10: ...FOLD PRESSURE FOR CORRECT INPUT RATE Tabulated Data Based on Altitude Up to 2000 Ft and 22 000 Btuh Per Burner GAS HEAT VALUE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 56 0 58 0 60 0 62 0 64 0 66 0...

Страница 11: ...uld be clear blue almost transparent See Fig 13 d High altitudes In the U S A gas input on rating plate is for altitudes up to 2000 ft Ratings for altitudes over 2000 ft must be 4 percent less for eac...

Страница 12: ...ingertight position only c Tighten thermocouple connection 1 4 turn with wrench d Relight pilot by following lighting instructions on the furnace 2 Check primary limit control This control shuts off t...

Страница 13: ...essure switch is functioning properly e Turn off 115 v power to furnace f Reconnect inducer motor wires replace control door and turn on 115 v power 5 Check auxiliary limits a Turn off 115 v power to...

Страница 14: ...1993 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 14 35003b Catalog No BDP 3339 607...

Отзывы: