background image

EXAMPLE:
Heat value = 980 Btu/cu ft
Specific gravity = 0.58
Therefore; Orifice No. 42 *

Manifold pressure 3.5-in. wc

* The furnace is shipped with No. 44 orifices. Therefore, in
this example all main burner orifices must be changed and
the manifold pressure must be adjusted.

(7.) Proceed to item c. to adjust manifold pressure.

b. Check gas input rate by clocking gas meter.

(1.) Obtain average yearly heat value for local gas

supply.

NOTE:

Be sure heating value of gas used for calculation is

correct for altitude. Consult local gas utility for altitude adjustment
of gas heating value.

(2.) Turn off all other gas appliances and pilots.

(3.) Start furnace and let run for 3 minutes.

(4.) Measure time (in sec) for gas meter to complete 1

revolution.

(5.) Refer to Table 7 for cu ft of gas per hr.

(6.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu

ft).

EXAMPLE:
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1070 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 72 sec
Gas rate = 100 X 1070 = 107,000 Btuh

(7.) Measured gas input should not exceed gas input on

unit rating plate.

(8.) Proceed to item c. to adjust manifold pressure.

c. Adjust gas input.

(1.) Remove regulator adjustment seal cap. (See Fig.

12.)

(2.) Turn adjusting screw counterclockwise to decrease

input. Turn screw clockwise to increase input. DO
NOT set manifold pressure less than 3.2-in. wc or
more than 3.8-in. wc for natural gas. Make any
major adjustments by changing main burner ori-
fices.

(3.) When correct input is obtained, replace regulator

seal cap. Main burner flame should be clear blue,
almost transparent. (See Fig. 13.)

d. High altitudes—In the U.S.A., gas input on rating plate

is for altitudes up to 2000 ft. Ratings for altitudes over
2000 ft must be 4 percent less for each 1000 ft above sea
level. To obtain the adjusted altitude rating, adjust the
manifold pressure, item c., and replace the main burner
orifice as needed. Refer to NFGC Appendix F, Table F-4
for proper orifice sizing at high altitudes.

e. Canadian installations only—The Canadian ratings are

approved for altitudes up to 2000 ft for natural and
propane gases. High-altitude ratings are from 2001 ft to
4500 ft above sea level. High-altitude input ratings
include a 10 percent derate as required by Canadian
standards. (See Table 8.)

2. Set temperature rise.

Do not exceed the temperature rise range specified on the
unit rating plate. Determine the air temperature rise as
follows:

a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
"see" heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.

Fig. 12—Redundant Automatic Gas Control Valve

A89171

PILOT

OFF

ON

THERMOCOUPLE

CONNECTION

PILOT
ADJUSTMENT
SCREW

MANUAL
ON/OFF
KNOB

INLET

PRESSURE

TAP

PILOT TUBE
CONNECTION

MANIFOLD
PRESSURE
TAP

REGULATOR 

ADJUSTMENT

SEAL  CAP

Fig. 13—Burner Flame

A84076

BURNER  FLAME

PILOT  FLAME

BURNER

MANIFOLD

—11—

Содержание 396HAD

Страница 1: ...t up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to the pot...

Страница 2: ...rther information the National Fuel Gas Code is available from National Fire Protection Association Inc Battery march Park Quincy MA 02269 American Gas Association 1515 Wilson Boulevard Arlington VA 2...

Страница 3: ...it must be installed so that the burners and ignition source are located at least 18 in above the floor The furnace should be protected from physical damage by vehicles When a furnace is installed in...

Страница 4: ...t opening directly communicating with the outdoors should be provided This opening should have a minimum free area of 1 sq in per 5000 Btuh of total input rating for all equipment in the enclosure If...

Страница 5: ...nnected to the furnace install the filters in a V formation inside the return air plenum See Fig 7 V GAS PIPING Gas piping must be installed in accordance with national and local codes Refer to the cu...

Страница 6: ...hin 72 in of the furnace A 1 8 in NPT plugged tapping accessible for test gage connection must be installed immediately upstream of the gas supply connection to the furnace and downstream of the manua...

Страница 7: ...link FL and limit switch LS to energize R With the furnace pilot lit the thermocouple will energize the thermal magnet circuit of gas valve GV permitting gas flow to the remaining portion of the gas...

Страница 8: ...h lighting operating instructions on the furnace The pilot flame should be soft blue in color and surround 3 8 in to 1 2 in of the thermocouple element tip The flame must never come in contact with an...

Страница 9: ...IVE BLADE TYPE FUSE FIELD INSTALLED FUSIBLE LINK GAS VALVE REDUNDANT HEATING FAN RELAY SPST N O INDUCED DRAFT MOTOR INDUCER DRAFT RELAY DPST N O BLOWER DOOR INTERLOCK SWITCH SPST N O JUNCTION BOX LIMI...

Страница 10: ...FOLD PRESSURE FOR CORRECT INPUT RATE Tabulated Data Based on Altitude Up to 2000 Ft and 22 000 Btuh Per Burner GAS HEAT VALUE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 56 0 58 0 60 0 62 0 64 0 66 0...

Страница 11: ...uld be clear blue almost transparent See Fig 13 d High altitudes In the U S A gas input on rating plate is for altitudes up to 2000 ft Ratings for altitudes over 2000 ft must be 4 percent less for eac...

Страница 12: ...ingertight position only c Tighten thermocouple connection 1 4 turn with wrench d Relight pilot by following lighting instructions on the furnace 2 Check primary limit control This control shuts off t...

Страница 13: ...essure switch is functioning properly e Turn off 115 v power to furnace f Reconnect inducer motor wires replace control door and turn on 115 v power 5 Check auxiliary limits a Turn off 115 v power to...

Страница 14: ...1993 BDP Co P O Box 70 Indianapolis IN 46206 Printed in U S A 14 35003b Catalog No BDP 3339 607...

Отзывы: