2.1.7
Wiring the Power Supplies and StepMetrix
Controller
—ATTENTION —————————————
⎯⎯⎯⎯⎯⎯
Do not apply DC power to controllers served by the power
supply until all connections have been made between the
power supply and the controller(s). If po wer is applied to a
controller before all connections have been made, the
power supply may become overloaded, causing a circuit
breaker to tri p or ot her power supply damage to res ult or
possibly causing damage to products served by the power
supply.
4. Wiring from the power supply to the controller box must
be run in conduit using 14 GA (2.5mm
2
) wire for the AC
Ground, DC Common, 12V and 24V.
5. Turn the voltage adjustment on the 12 V power supply
counter clockwise. This is done to re duce power
dissipation in the enclosure.
6. Connect the AC Ground, DC Common, 12V and 24V to
the terminal block in controller.
— NOTE ———————————————————
⎯⎯⎯
The following colors are recommended
AC ground
Green or green/yellow if required
by code
2.1.7.1
Load Cell to StepMetrix Controller Connections
•
The load cells for the StepMetrix se nsor module
are numbered 1-8. They are numbered with
respect to the location of the ¾ ” (19 mm) conduit,
as shown in Figure 13.
DC common
Black/white
+12 Volts DC
Pink/white
+24 Volts DC
Red/white
•
Each load cell is connected to a connector on the
load cell signal conditioning board.
1. Mount the p ower supplies in the enc losure that’s
provided. Mount it in a dr y location no mo re than 5 0
feet (15 m) from the StepMetrix controller.
•
The load cell signal conditioning board, located in
the StepMetrix controller, has fo ur 10-pin
connectors (J101 to J10 8), as shown in Figures
14 and 14a.
2. Connect the power supply to 220-240VAC, following all
applicable codes, as shown in Figure 12.
•
Connect individual load cell cables to the pins, as
shown in Figure 14a.
3. Connect DC Common between the 12V and 24V power
supplies. Use 14 GA (2.5 mm
2
) wire.
11.
Installing the StepMetrix™ controller l864_11
StepMetrix™ Installation Instructions
9E-864C
11
Содержание StepMetrix
Страница 13: ...14 Wiring diagram label P N 3558769 l864_14 StepMetrix Installation Instructions 9E 864C 13 ...
Страница 14: ...9E 864C StepMetrix Installation Instructions 14 14b The control assembly l864_14b 14a Load cell board l864_14a ...
Страница 20: ...9E 864C StepMetrix Installation Instructions 20 21 Load cell locations l864_24 ...
Страница 21: ...22 ISO ID wiring wiring diagram label P N 3559299 l864_25 StepMetrix Installation Instructions 9E 864C 21 ...
Страница 22: ...9E 864C StepMetrix Installation Instructions 22 24 The control assembly l864 27 23 Load cell board l864_26 ...