33
Service menu
Sense II – 6 720 818 367 (2015/10)
7.1.3 Heating circuit 1 – 4
Settings for individual heating circuits can be made in this
menu. For example, it can be set whether a remote control is
available and which control type is used e.g. Sense I. There is
also the possibility to optimise the heating curve of the heating
circuits.
3 WV centre pos.
Yes
3-way valve in centre position
No
Emerg. altern. op.
Yes
If the DHW cylinder takes a long time to charge, alternating operation between
DHW heating and CH occurs to ensure that central heating demand is met
despite the fact that DHW priority is set.
No
Turbine signal delay time
0.5
... 4 s
DHW Flow Turbine signal delay in seconds
Menu item
Adjustment range description
Table 19 Settings in the boiler data menu
NOTICE:
Risk of damaging the screed!
▶ If an underfloor heating system is used,
the max. flow temperature recommended
by the manufacturer of the system should
be observed. A temperature limiting
device must be used.
Menu item
Adjustment range
description
Heating circuit
installed
No
Heating circuit is not installed. If no heating circuit is installed, the heat source only
serves DHW heating.
At the boiler
Electrical assemblies and components of the selected heating circuit are directly
connected to the heat source (only available with heating circuit 1).
At the module
Electrical assemblies and components of the selected heating circuit are
connected to an MM 100/MM 200 module.
Ctrl type h.
circ. 1
Outdoor-temp.-
compensated
Further information on the control type
Outside temp. with low end
Room-temp.-compensated
Room temperature output
Constant
Prog. unit heat.
circ. 1
Sense II
Sense II controls the selected heating circuit without remote control.
Sense I
Sense I is installed as remote control unit for the selected heating circuit.
Use minimum
value
Yes
A Sense II controller in combination with a Sense I (Sense I set to “remote
control”) is installed in the living space. The heating system is operated according
to the lower room temperature value (measured at the internal temperature
sensor at both user interfaces) (e.g. in large rooms for a safe recording of the room
temperature with room temperature-dependent control, room frost protection,
room influence, ...).
No
A Sense II controller in combination with a Sense I (Sense I set to “remote
control”) is installed in the living space. The heating is always operated according
to the room temperature value of the remote control.
Heating system
heat circ. 1
Radiator
Factory default of the heating curve adjusted depending on heat emitter type
Convector heater
Underfloor
Set point
constant
30 ...
75
... 85 °C
Flow temperature for constant heating circuit (only available with Constant control
type)
Table 20 Check settings in the heating circuit 1 – 4