Installation
Sense II – 6 720 818 367 (2015/10)
3.9
Installation of an outside temperature sensor
If the controller is to be used as a weather-compensated
controller, the outside temperature sensor, supplied, is
required.
To correctly record the outside temperature:
▶ Observe the points represented in Fig. 14 when selecting
the correct installation location of the outside temperature
sensor.
The
outside temperature sensor
is connected to the heat
source.
▶ Observe the instructions for the heat source when
connecting the electrical supply.
When sensor leads are extended, apply the following cable
cross-sections:
•
Up to 20 m with 0.75 mm
2
to 1.50 mm
2
conductor cross-
section
•
20 m up to 100 m with 1.50 mm
2
conductor cross-
section.
Fig. 14
Installation location for the outside temperature sensor (for weather-compensated control with or without room
temperature influence)
1
/
2
H
(min 2m)
H
1
/
2
Y
Y
1
/
2
H
(min 2m)
H
N
S
W
E
NW
NE
SW
SE
6 720 812 360-07.1O