22
Commissioning
Sense II – 6 720 818 367 (2015/10)
Menu item
Question
Answer/setting
Start configuration wizard
Check before starting the configuration wizard:
•
Module installed and coding address set (E.g.
MS100)?
•
Remote control installed and set (E.g. Sense I)?
•
Temperature sensor installed (e.g. solar collector,
low loss header or DHW sensor)?
Start the configuration wizard?
Yes
|
No
System data
Low loss hdr.
sensr. instll.
Is a low loss header installed? If yes, is a temperature
sensor installed? If yes, where is it electrically
connected to?
No low-loss header
|
At the
boiler
|
At the module
|
Header w/
o sensor
Config. DHW
at boiler
How is DHW connected to the heat source (boiler)?
No DHW
|
3-way valve
|
Primary
pump
Config. of HC1
at boiler
Is heating circuit 1 connected to the heat source
(boiler)? If yes, does the heating circuit rely on the
boiler pump (no own heating circuit pump) or a
separate, dedicated heating circuit pump (own
pump)?
No heating circuit
|
No own
heating circuit pump
|
Own pump
Min. outdoor
temperature
With weather-compensated control: What is the
minimum outside temperature at the location
averaged over the last years?
– 35 – 10 °C
Type of
building
How well insulated is the building?
Light
|
Medium
|
Heavy
Boiler data
Pump type
Is the pump operated depending on the burner output
or by differential pressure?
Output-compensated
|
Delta P-
compensated 1 – 4
Pump run-on
time
How long should the pump over-run be in order to
discharge the heat from the heat source?
24h
|
1 – 60 min
Heating circuit 1 Heating circuit
installed
Is heating circuit 1 installed? If yes, where is heating
circuit 1 electrically connected?
No
|
At the boiler
|
At the module
Ctrl type h.
circ. 1
How should the temperature influencing heating
circuit 1 be controlled?
Outdoor-temp.-compensated
|
Outside temp. with low end
|
Room-temp.-compensated
|
Room temperature output
|
Constant
Prog. unit
heat. circ. 1
What controller is installed?
Sense II | Sense I
Heating
system heat
circ. 1
What type of heat emitter does heating circuit 1
operate with?
Radiator
|
Convector heater
|
Underfloor
Set point
constant
If heating circuit 1 is configured as constant heating
circuit: To what temperature should the heating be
controlled?
30
–
85 °C
Max. flow
temperature
What is the maximum flow temperature that should be
set?
For example
30 – 85 °C
Set heating
curve
Should the heating curve for heating circuit 1 be set?
(For further sub-settings
Chapter 7.1.3, starting on
Table 14 Commissioning with the configuration wizard