Configuration, Installation, and Startup of an Inline System (Example)
Application Description
|
Inline
Electric Drives |
Bosch Rexroth AG
and Controls
8.3
Selecting Accessories
8.3.1
Power Supplies
The selection of suitable power supplies always depends on the individual system.
24 V DC power supplies should however always satisfy the following criteria:
Electrical isolation
If electrical isolation is required between logic and I/O, you must provide the bus
coupler supply U
BK
and the I/O supply U
M
/U
S
from separate power supply units.
If you want to set up various electrically isolated areas within an Inline station, you
must use additional power terminals that are supplied from separate power supply
units.
Example project
Logic and I/O are to be electrically isolated in an Inline station. They must therefore
be supplied from separate voltage sources.
The logic current consumption of the terminals is 337 mA corresponding to the
table
"Current consumption in the example project" on page 41
.
8.3.2
End Clamps and Labeling Fields
Two end clamps are needed to secure an Inline station on the DIN rail. Mount
these on both sides of the Inline station to keep it from moving from side to side.
Depending on the mounting position, Bosch Rexroth recommends SUB-M01-
ENDHALTER (MNR R911170685) end clamps for mounting on a horizontal DIN
rail; snapped on without tools or SUB-M01-ENDHALTER/AL (MNR R911171035)
end clamps for mounting on a vertical DIN rail; secured with screws.
8.3.3
Minimizing Interference
Correct installation and assembly can minimize electromagnetic interference.
When installing an Inline station, please observe the grounding and shielding
measures described in the DOK-CONTRL-ILSYSINS***-AW..-EN-P application
description.
Information on the individual circuits in a Inline station can be found in
the DOK-CONTRL-ILSYSINS***-AW..-EN-P application description.
For additional information about the connection of the various supply
voltages, please refer to
Chapter 6.1, "Connecting the Voltage
.
Nominal value:
24 V DC
Ripple:
± 5%
Permissible range:
19.2 V to 30 V (ripple included)
Содержание Rexroth Inline Series
Страница 6: ...Table of Contents 6 6 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 58: ...Examples and Tips 52 58 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 62: ...Service Support 56 58 Bosch Rexroth AG Electric Drives R IB IL INC PAC Anwendungsbeschreibung and Controls ...
Страница 63: ...Notes Application Description Inline Electric Drives Bosch Rexroth AG 57 58 and Controls ...