Integration of Inline Into the INTERBUS System
Bosch Rexroth AG
| Electric Drives
Inline
|
Application Description
and Controls
3.3.3
System Requirements
Controller board
A controller board with firmware Version 4.40 or later is required to operate the
INTERBUS system. A Generation 4 (G4) controller board must therefore be used
that can be operated with this firmware version.
ILC/FC/RFC
Firmware Version 4.4x or later is required to operate an Inline Controller, Field
Controller or Remote Field Controller. A controller that can be operated with this
firmware version must be used.
3.3.4
Product Description
Within the Inline product family, automation terminals are available for I/O
functions, special functions, and control functions.
Automation terminals consist of an electronics base and one or more connectors
for connecting the I/O devices or the power supply. The electronics base can be
replaced without removing a single wire from the connector.
The Inline terminals are connected to INTERBUS via a bus coupler. Up to 63 local
bus devices can be connected to a bus coupler as long as the limit parameters are
Chapter "Number of devices" on page 20
Versions
The product range offers terminals for all automation tasks:
•
Bus couplers for connecting the Inline station to the INTERBUS remote bus.
The remote bus uses copper technology.
•
Terminals with remote bus branch for opening a remote bus branch. The
remote bus branch uses copper technology.
•
Supply terminals for supplying the supply voltages and segmenting the
station (with and without fuse)
•
Input and output terminals for digital and analog signals
•
Function terminals (e.g., counters, incremental encoders)
•
Branch terminals for integrating a Fieldline Modular local bus
Mounting location
Inline terminals (IP20 protection) are designed for use in closed housing. The
compact structure means that most of the Inline terminals can be installed in
standard terminal boxes.
Assembly
Inline terminals can be snapped onto DIN rails without tools. Potential and data
jumpers are automatically created when the terminals are properly installed.
Bus connection
The Inline station is connected to the remote bus via a bus coupler. The bus is
controlled by the Inline station through data routing.
I/O connection
The Inline terminals have connectors for 1, 2, 3, and 4-wire sensors or actuators.
The wires are connected using spring-cage technology. For more detailed
information, please refer to the individual chapters.
Содержание Rexroth Inline Series
Страница 6: ...Table of Contents 6 6 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 58: ...Examples and Tips 52 58 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 62: ...Service Support 56 58 Bosch Rexroth AG Electric Drives R IB IL INC PAC Anwendungsbeschreibung and Controls ...
Страница 63: ...Notes Application Description Inline Electric Drives Bosch Rexroth AG 57 58 and Controls ...