Diagnostic and Status Indicators
Bosch Rexroth AG
| Electric Drives
Inline
|
Application Description
and Controls
7.1
Diagnostic Indicators on Bus Couplers
Fig. 7-1
Indicators on the bus coupler
(e.g., R-IBS IL 24 BK-T/U-PAC)
The following states can be read on bus couplers:
1
2
1
1
1
2
1
1
1
2
1
1
1
2
1
1
5520D050
UL
UM
US
BA
RC
RD
LD
UL
US
UM
BK-T/U
1
3
5
6
2
7
4
BA (1)
Green LED
Remote bus active
ON:
Data transmission on INTERBUS
(INTERBUS state: Run)
Flashing:
ID cycle; no data transmission
(INTERBUS state: Active)
OFF:
No data transmission
RC (2)
Green LED
Remote bus connection (remote bus check)
ON:
Incoming remote bus connection established
OFF:
Incoming remote bus connection faulty
RD (3)
Yellow LED
Remote bus disabled
ON:
Outgoing remote bus interface disabled
OFF:
Outgoing remote bus interface not disabled
LD (4)
Red or
yellow LED
Local bus disabled
ON yellow:
Local bus disabled
ON red:
Isolated disconnection of local bus after error
OFF:
Local bus not disabled
UL (5)
Green LED
Bus coupler supply/communications power/interface supply
ON:
Supply present
OFF:
Supply is not present
Additionally on bus couplers with copper remote bus connections
US (6)
Green LED
Supply in the segment circuit
ON:
Supply is present in the segment circuit
OFF:
Supply is not present in the segment circuit
UM (7)
Green LED
Supply in the main circuit
ON:
Supply is present in the main circuit
OFF:
Supply not present in the main circuit
Содержание Rexroth Inline Series
Страница 6: ...Table of Contents 6 6 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 58: ...Examples and Tips 52 58 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 62: ...Service Support 56 58 Bosch Rexroth AG Electric Drives R IB IL INC PAC Anwendungsbeschreibung and Controls ...
Страница 63: ...Notes Application Description Inline Electric Drives Bosch Rexroth AG 57 58 and Controls ...