Configuration, Installation, and Startup of an Inline System (Example)
Bosch Rexroth AG
| Electric Drives
Inline
|
Application Description
and Controls
8.2
Selecting the Required I/O Terminals
8.2.1
Inline Station Devices
Select the appropriate Inline terminals for the I/O signals in your project.
Task point 1: 12 digital inputs
Task point 2: Initiator supply
Task point 3/1: 6 digital outputs, lamp load of 0.5 A each
Task point 3/2: 5 digital outputs > 0.5 A
Task point 4: 2 channels for temperature measurement
Requirements met?
Possible terminals
4-wire technology
12 channels
... DI 4/... DI 16
No
... DI 2/... DI 8
Yes
1 x DI 8 and 2 x DI 2
Requirements met?
Possible terminals
Short-circuit
proof
Diagnostics via
INTERBUS
... SEG
No
No
... SEG/F
Yes
No
... SEG/F-D
Yes
Yes
Requirements met?
Possible terminals
Load current up
to 0.5 A
Reserve
... DO 2-2A
No (2 A not
required)
... DO 4
Yes
No
... DO 8/... DO 16
Yes
Yes
Requirements met?
Possible terminals
Load current
> 0.5 A
High degree of
simultaneity
5 channels
... DOR 1/W
Yes
–
... DO 2-2A
Yes
Yes
3 x DO 2-2A
... DO 8-2A
Yes
No
... DO 4/ 8/16
No
Yes
Requirements met?
Possible terminals
Temperature
Range
0°C to 120°C
Rate of change
2 channels
... TEMP 2 RTD
-200°C to +850°C
Low
1 x TEMP 2 RTD
... TEMP 2 UTH
> +850°C
(not required)
High
(not required)
Содержание Rexroth Inline Series
Страница 6: ...Table of Contents 6 6 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 58: ...Examples and Tips 52 58 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 62: ...Service Support 56 58 Bosch Rexroth AG Electric Drives R IB IL INC PAC Anwendungsbeschreibung and Controls ...
Страница 63: ...Notes Application Description Inline Electric Drives Bosch Rexroth AG 57 58 and Controls ...