Mounting/Removing InlineTerminals and Connecting Cables
Bosch Rexroth AG
| Electric Drives
Inline
|
Application Description
and Controls
6.1.2
Notes on Supply Voltages
The bus coupler supplies the module electronics of the connected terminals with
communications power (U
L
), which is generated from the bus coupler supply
voltage (e.g., U
BK
). If this supply voltage is disconnected, the bus stops.
The supply voltage to the sensors and actuators (U
M
/U
S
) should be installed and
protected independently of the bus coupler supply (U
BK
). In this way INTERBUS
continues to run even if some I/O devices are switched off.
6.2
Connecting the Bus
The INTERBUS remote bus is connected to a bus coupler. Bus couplers are
available for connecting the remote bus using copper or fiber optic technology.
Remote bus using copper
technology
The bus cables are shielded cables. They are connected via an Inline connector
with shield connection or via a D-SUB connector.
Connection via an Inline connector is the same as the connection of shielded
cables via a shield connector and is described in the DOK-CONTRL-ILSYSINS***-
AW..-EN-P application description.
Connection via a D-SUB connector is described in the terminal-specific data
sheet.
6.3
Connecting I/O Devices
To connect the sensors and actuators, proceed as described in the DOK-
CONTRL-ILSYSINS***-AW..-EN-P application description.
For the assignment of the connections and terminal points, please
refer to the relevant bus coupler data sheet.
Содержание Rexroth Inline Series
Страница 6: ...Table of Contents 6 6 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 58: ...Examples and Tips 52 58 Bosch Rexroth AG Electric Drives Inline Application Description and Controls ...
Страница 62: ...Service Support 56 58 Bosch Rexroth AG Electric Drives R IB IL INC PAC Anwendungsbeschreibung and Controls ...
Страница 63: ...Notes Application Description Inline Electric Drives Bosch Rexroth AG 57 58 and Controls ...