Table 4.10
SMS and USB Configuration Parameters
4.3
Polling Configurations
Plan carefully when selecting the control panel poll time, ACK wait times, control panel
retries, ITS-DX4020-G GPRS ACK timeouts, and D6x00 Receiver poll and ACK wait times.
Having the wrong or improper settings could cause trouble conditions when the network
carrier performs maintenance, and increased data volumes could affect your monthly cost.
Your settings for these parameters determine how the system works, but depend on the
security level needed.
4.3.1
High Security Application (bank, jewelry store, UL fire, and so on)
Polling times are typically less than 20 min. Path integrity is critical, and short interruptions in
network service are indicated at the premise and central station. The following High Security
Application recommendation assumes the ITS-DX4020-G is the primary communication device
with no backup.
Control Panel Settings
–
Poll Rate:
60 sec
–
ACK Wait:
13 sec
–
Retry Count:
5
ITS-DX4020-G Settings
–
GPRS ACK Timeout:
ACK wait (13) x Retry Count (5) + ACK Wait (13) = 78 sec
–
GPRS Session Timeout:
Must be greater than control panel poll time (60 sec) + GPRS
ACK timeout (78 sec). The minimum GPRS session timeout setting is 1 hour; the default
4 hour setting is acceptable.
D6x00 Receiver Settings
–
Control Panel Poll Rate:
60 sec
–
ACK Wait:
78 sec
63
Dynamic DNS ID
Selection
–
1 = SIM ICCID
–
2 = ID is SIM IMSI
–
3 = ID is modem IMEI
–
4 = ID is manually entered
Select a DNS ID method.
64
Dynamic DNS ID
2 to 20 characters
Must conform to RFC952 and RFC1123 name
format.
NOTICE!
This field is required only if parameter 63 is set to 4.
ID