100
en | Installation of the Pipe System
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
–
Position the tap lever so that the blast air and pipe system are connected (B-C
connection).
The connection to the
FCS-320
must be blocked for blowing-out!
Manually blow out the pipe system for approximately 10 seconds.
–
Set the lever of the tap such that the device is not connected with the pipe system or
with the connection for the blast or compressed air supply. Wait approximately 20
seconds so that dust and dirt raised in the pipe system can settle and thus will not be
sucked through the aspirating smoke detector.
–
Reconnect the blown-out pipe system to the FCS-320 within a further 10
seconds by
switching over the tap accordingly (A‑C connection).
6.8
FAS‑ASD‑WS Water Separator
FAS‑ASD‑WS Water Separator
The FAS‑ASD‑WS Water Separator must be fitted at the lowest point in the pipe system
downstream of the air filter and the aspirating smoke detector (see figure below).
1
2
3
3
FA
S-420
se
rie
s
Installing the FAS‑ASD‑WS Water Separator in the pipe
system
1
FAS‑ASD‑WS Water
Separator
2
Pipe system connection
3
45° pipe elbow
Connection
Attach two 45° pipe elbows on both sides (
not
supplied as standard) in order to achieve the
optimum distance from the wall for mounting the brackets. When installing, note the correct
direction of flow (see arrow on plastic container).
Also fasten the water separator with two screws and the clamp.
To empty, open the drain valve.