3.5.5
FAS-ASD-DIAG Diagnostic Software
DIAG
Figure
3.4: Diagnostic software for reading out unit status
The diagnostic software enables the saved and the current unit status, as well as the error
messages to be displayed on the PC or laptop.
The supplied diagnostics cable connects the aspirating smoke detector ("DIAG" connection on
the motherboard) to the PC. The FAS-ASD-DIAG version is connected to the PC via a USB port,
earlier DIAG versions via a COM port.
Diagnostic messages remain saved in the unit for at least 3 days in order to be able to evaluate
even short, sporadically occurring errors (e.g. in case of changed operating conditions).
Resetting the device via the diagnostic software deletes all saved diagnostic messages.
The software also allows the deletion of error messages.
Notice!
The diagnostic software can be used to save in file format all the stored and current
diagnostic data as well as any settings made. To be able to compare the data read out, save
each file under a different file name.
3.5.6
Remote indictors
A remote indicator must be connected if the aspirating smoke detector is not directly visible
or has been mounted in false ceilings or floors.
The external detector alarm display is installed in an obvious place in halls or entrances of the
building section or areas concerned.