Aspirating Smoke Detector
Installing the Aspirating Smoke Detector | en
81
Bosch Sicherheitssysteme GmbH
Operation Guide
2018.04 | 2.0 | F.01U.130.926
Aspiration from below
If the air-return pipe is directed upwards, it must be guaranteed that no foreign bodies or
dripping water can penetrate the air return. You should therefore use a short, downward
angled pipe.
Mounting type MT-1
The aspirating smoke detector is either bolted directly to the wall provided for installation
using the rear panel or installed by means of unit mounting type MT-1, e.g. onto frames.
1
2
FA
S-4
20
ser
ies
FA
S-4
20
ser
ies
Installing on mounting type MT-1
1
Horizontal installation
2
Vertical installation
Installation material FCS-320
Cylinder or flat head screws
–
Thread diameter: max. 6
mm
–
Head diameter: 10
mm
Mounting (type MT-1)
Cylinder or flat head screws
–
Thread diameter: max. 4
mm
–
Head diameter: 5 to 7
mm
Bore distances
The distances between the bores are shown in the figures below (all measurements in mm).
3
0
255
160
200
292
Figure
5.2: Bore distances of FCS-320 without mounting
Содержание FAS-420
Страница 1: ...Aspirating Smoke Detector FCS 320 TP1 FCS 320 TP2 en Operation Guide ...
Страница 2: ......
Страница 132: ...132 en Index Aspirating Smoke Detector 2018 04 2 0 F 01U 130 926 Operation Guide Bosch Sicherheitssysteme GmbH ...
Страница 133: ......