44
en | Planning
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
Limiting values
Min. distance: FCS-320 – 1st air sampling opening
4
m
I-pipe system
Max. distance: FCS-320 – 1st air sampling opening
20
m
Max. distance: 1st air sampling opening – last air sampling opening
–
With low fan voltage
–
With high fan voltage
56
m
80 m
Max. overall pipe length per pipe system (Ø 25
mm)
–
With low fan voltage
–
With high fan voltage
76
m
100
m
Min. distance between 2 air sampling openings
4
m
Max. distance between 2 air sampling openings
12
m
Max. number of air sampling openings (n) per pipe system
13
I-pipe system Air sampling
opening
Number of air sampling openings
1
2
3
4
5
6
7
8
9
10 11 12 13
∅
air sampling
opening in
mm
a
A
7.0 6.0 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5 2.5
B
6.8 5.2 4.6 4.2 3.8 3.6 3.4 3.0 3.0 2.5 2.5 2.5
C
5.6 4.6 4.4 4.0 3.8 3.4 3.2 3.0 3.0 3.0 2.5
D
5.0 4.4 4.0 3.8 3.4 3.4 3.0 3.0 3.0 2.5
E
4.4 4.2 3.8 3.6 3.6 3.4 3.0 3.0 3.0
F
4.2 3.8 3.8 3.6 3.4 3.4 3.0 3.0
G
4.0 3.8 3.6 3.6 3.4 3.2 3.0
H
4.0 3.8 3.6 3.4 3.2 3.0
I
3.8 3.6 3.6 3.2 3.2
J
3.8 3.8 3.2 3.2
K
3.8 3.8 3.4
L
4.0 3.8
M
4.0
a
Punch diameter of the aspiration reducing film sheet