Aspirating Smoke Detector
Planning | en
47
Bosch Sicherheitssysteme GmbH
Operation Guide
2018.04 | 2.0 | F.01U.130.926
M-pipe system
Air sampling opening Number of air sampling openings
3
6
9
12
15
18
21
∅
air sampling
opening in mm
a
A
4.4
3.4
3.0
2.5
2.5
2.0
2.0
B
3.6
3.0
2.5
2.5
2.5
2.0
C
3.2
3.2
2.5
2.5
2.0
D
3.2
3.0
2.5
2.5
E
3.2
3.0
2.5
F
3.2
3.2
G
3.4
a
Punch diameter of the aspiration reducing film sheet
Double U-pipe system for space protection
1 pipe system
FCS-320-TP1
FCS-320-TT1
2 pipe systems
FCS-320-TP2
FCS-320-TT2
FAS / FCS
FAS / FCS
F
F
B
B
A
A
Double U-pipe system for space protection
Limiting values
Min. distance: FCS-320 – last T-fitting
4
m
Double U-pipe
Max. distance: FCS-320 – last T-fitting
20 m
Max. branch length
–
With low fan voltage
–
With high fan voltage
40
m
45
m
Max. overall pipe length per pipe system (Ø 25
mm)
–
With low fan voltage
–
With high fan voltage
180
m
200
m
Min. distance between 2 air sampling openings
4
m
Max. distance between 2 air sampling openings
12
m
Max. number of air sampling openings (n) per pipe system
24