4
5 6
7 8
9 1
0
Double U-pipe system, e.g. for equipment protection
Limiting values
Min. distance FCS-320 – last T-fitting
2
m
Double U-pipe
Max. distance FCS-320 – last T-fitting
20
m
Max. branch length
20
m
Max. overall pipe length (Ø 25
mm)
100
m
Min. distance between air sampling openings (d)
0.1
m
Max. distance between air sampling openings (d)
4
m
Max. number of air sampling openings (n) per pipe system
20
Double U-pipe
Number of air sampling openings
4
8
12
16
20
Ø of all air sampling openings in mm
a
4.0
3.4
3.0
2.5
2.0
a
Punch diameter of the aspiration reducing film sheet
See also
–
Standard Pipe Planning, page 39
4.9
Planning for Long Pipe Feed Lines
Pipes with a 40
mm diameter are required for planning pipe feed line A. Area B is designed
with 25
mm pipes in accordance with Standard Pipe Planning. The plan applies for the pipe
configurations described above.