48
en | Planning
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
Double U-pipe
system
Air sampling opening Number of air sampling openings
4
8
12
16
20
24
∅
air sampling
opening in mm
a
A
4.0
3.0
2.5
2.0
2.0
2.0
B
-
3.4
3.0
2.5
2.0
2.0
C
-
-
3.0
3.0
2.5
2.0
D
-
-
-
3.2
2.5
2.5
E
-
-
-
-
3.6
2.5
F
-
-
-
-
-
3.6
a
Punch diameter of the aspiration reducing film sheet
Quadruple U-pipe system for space protection
1 pipe system
FCS-320-TP1
FCS-320-TT1
A
B
C
D
FAS / FCS
Quadruple U-pipe system for space protection
Limiting values
Min. distance: FCS-320 – last T-fitting
4
m
Double U-pipe
Max. distance: FCS-320 – last T-fitting
20 m
Max. branch length
–
With high fan voltage
35
m
Max. overall pipe length per pipe system (Ø 25
mm)
–
With high fan voltage
300
m
Min. distance between 2 air sampling openings
4
m
Max. distance between 2 air sampling openings
12
m
Max. number of air sampling openings (n) per pipe system
32
Содержание FAS-420
Страница 1: ...Aspirating Smoke Detector FCS 320 TP1 FCS 320 TP2 en Operation Guide ...
Страница 2: ......
Страница 132: ...132 en Index Aspirating Smoke Detector 2018 04 2 0 F 01U 130 926 Operation Guide Bosch Sicherheitssysteme GmbH ...
Страница 133: ......