en | Installing the Aspirating Smoke Detector
Aspirating Smoke Detector
2018.04 | 2.0 | F.01U.130.926
Operation Guide
Bosch Sicherheitssysteme GmbH
Sensitivity
DIP settings
DM-TP-01(05)
DM-TT-01(05)
DM-TP10(25)
DM-TT-10(25)
DM-TP50(80)
DM-TT-50(80)
Switch 1
Switch 2
0.12%/m
(0.4%/m)
0.8%/m
(2%/m)
-
on
on
0.06%/m
(0.2%/m)
0.4%/m
(1%/m)
-
off
on
0.03%/m
(0.1%/m)
0.2%/m
(0.5%/m)
1.0%/m
(1.6%/m)
on
off
0.015%/m
(0.05%/m)
0.1%/m
(0.25%/m)
0.5%/m
(0.8%/m)
off
off
Alarm delay
DIP settings
Switch 3
Switch 4
0 seconds
off
off
10 seconds
on
off
30 seconds
off
on
60 seconds
on
on
Activation threshold for airflow malfunction
DIP settings
Switch 5
Switch 6
Low (+/- 10% volume flow change)
on
off
Average (+/- 20% volume flow change)
off
on
High (+/- 30% volume flow change)
off
off
Very high (+/- 50% volume flow change)
on
on
Airflow fault delay
DIP settings
Switch 7
Switch 8
30 seconds
off
on
2 minutes
on
off
15 minutes
on
on
60 minutes
off
off
Trouble logging
DIP settings
LOGIC·SENS filter
DIP settings
Switch 9
Switch 10
not saving
off
off
off
saving
on
on
on