D7212GV3 |
Program Entry Guide | 2.0
Panel and Area Wide Parameters
EN
| 71
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Unlike the default relay for Alarm Bell and Fire Bell,
this voltage-output relay (Relay C) de-activates for 5
sec when the
Reset Sensors?
function is activated
from the keypad or during a Fire Walk Test.
The Reset Sensors time converts from
the 5 sec default time to the time
programmed in
A# Verify Time
(
Section
2.8 Area Parameters
on page
5
) when a
point programmed for
P## Alarm Verify
(
Section 4.1 Point Index
on page 77)
enters an alarm condition.
When sharing one relay to reset sensors
in two or more areas, you must program
the following. Failure to do so causes
TROUBLE PT ### for all point types
programmed as
P## Resettable
.
CC # Scope
must include all areas
that share the relay.
L## Reset Sensors
authority must be
assigned to the passcode that
activates the COMMAND 47 or Reset
Sensor function.
A# Verify Time
must be the same
number of seconds for all areas that
share the relay.
A# Fail to Close
Default:
0
Selection:
0, 1 to 24, A, B, or C
This relay activates when the Closing Window
expires for the specified area. It remains active until
midnight, another Closing Window starts, or the
control panel resets, whichever occurs first. When
Perimeter Relay
(refer to page 126) is set to
Yes
,
the
A# Fail to Close
prompt becomes
A# Perimeter
Relay
when using firmware version 8.0 and later.
A# Force Armed
Default:
0
Selection:
0, 1 to 24, A, B, or C
This relay activates when this area is Force Armed. It
remains active until the area disarms or the control
panel resets.
If Force Bypassing is required during
Perimeter Arming, this relay does not
activate.
A# Watch Mode
Default:
0
Selection:
0, 1 to 24, A, B, or C
This relay activates when a Controlled point
programmed for
P## Watch Point
is faulted in the
specified area while the area is in Watch Mode and
the point is not armed. It remains active for 2 sec
after each point is faulted.
A# Area Armed
Default:
0
Selection:
0, 1 to 24, A, B, or C
This relay activates when the specified area becomes
Master Armed. The exit delay must expire before the
relay activates. The relay remains active until the
area disarms. It does not deactivate during the entry
delay time.
If multiple areas use the same relay, the relay
activates when all areas are armed. It deactivates
when the first area disarms.
The
A# Area Armed
relay function can provide visual
feedback at a key switch station. Attach a LED to the
output of a D8129 Module programmed for this
function.
A# Area Fault
Default:
0
Selection:
0, 1 to 24, A, B, or C
Activates whenever a controlled (
P## Type 1, 2, 3
only) Perimeter or Interior point is faulted. The relay
remains active until all Perimeter and Interior points
in the area are normal.
Keyswitch area armed status with
LEDs:
Use a D8129 Module and connect
an LED to indicate that the area is not
ready to arm.
A# Duress Relay
Default:
0
Selection:
0, 1 to 24, A, B, or C
Activates when a Duress alarm is generated from a
keypad assigned to the specified area.
Burg Time needs a bell period
programmed and
A# Duress Enable
must be
Yes
. This relay activates when
the Burg Bell starts and deactivates when
the Burg Bell time ends. The Burg Bell
pattern has no effect on this relay
function.