![Bosch D7212GV3 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/bosch/d7212gv3/d7212gv3_program-entry-manual_39294019.webp)
D7212GV3 |
Program Entry Guide | 2.0
Panel and Area Wide Parameters
EN
| 19
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Diagnostic Reports
Selecting
Yes
enables sending a report when the
event occurs. If the off-normal state of any events
indicated by footnote 1 in
Table 10
still exists, the
events report when a Test Report is enabled and
Expanded Test Report
is programmed
Yes
. Refer to
the
Test Reports
sub-prompt in
Section 2.3.8
Communication Attempts
on page 14.
Table 10: Diagnostic Reports
Report Selections
Report
Description
R# SDI Dev Fail
1
Yes
, No
SDI device
failure
R# SDI Dev Restl
Yes
, No
Restoral of SDI
device failure
R# Watchdog
Rset
Yes
, No
Watchdog
Reset Event
R#
ParaChksmFail
Yes
, No
Parameter
checksum
failure
R# Reboot
Yes
, No
Reboot Event
R# Ph Line Fail
1
Yes
, No
Failure of phone
line
R# Ph Line Rstl
Yes
, No
Restoral of
phone line after
failure
R# AC Fail
1
Yes
, No
Failure of AC
power to control
panel
R# AC Restorl
Yes
, No
Restoral of AC
power to control
panel after
failure
R# Batt Missing
1
Yes
, No
Battery Missing
Detection Event
R# Battery Low
1
Yes
, No
Low battery
power
R# Battery Rstl
Yes
, No
Restoral of
battery power to
control panel
after Missing or
Low Event
R# Rt Comm
Fail
1, 2
Yes
, No
Failure to send
report to specific
route
R# Rt Comm Rstl
Yes
, No
Restoral of
communication
to specific route
after a failure
Table 10: Diagnostic Reports (continued)
R# Checksum Fail
Yes
, No
Checksum Fail
Event
R# Network Fail
3
Yes,
No
Failure of
network
R# Network Rest
3
Yes,
No
Restoral of
network
R# Network Cond
3
Yes,
No
Condition of
network
1
This event is included in the Expanded Test Report
when an off-normal condition exists.
2
This event covers Comm Fail Route Group and Comm
Fail Phone. If enabled, both events are sent; if
disabled, neither event is sent.
3
This event is reserved for future use.
Enable Rt Comm Fail and Rt Comm
Restore in only one route group.
Relay Reports
Selecting
Yes
enables sending a report when the
event occurs.
Table 11: Relay Reports
Report Selections
Report
Description
R# Sensor
Reset
Yes
, No
Sensor Reset
Event
R# Relay Set
Yes
, No
Relay Set Event
R# Relay
Reset
Yes
, No
Relay Reset Event
When activating an on-board relay using
remote automation software, the
D7212GV3 Control Panel logs and prints
the event as:
Relay 250
Relay A
Relay 251
Relay B
Relay 252
Relay C