D7212GV3 |
Program Entry Guide | 2.0
Panel and Area Wide Parameters
EN
| 66
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
L## Change Relay
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
28 Change
Relays
[COMMAND][5][4]
Manually activate or reset a system relay.
Do
not
use the Change Relays? function
to toggle relays reserved for special
functions. Special function relays are
Area and Panel Wide Relay functions as
well as relays assigned to
CC# Enter
Key Relay?
L## Remote Program
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
29
Remote
Programming
[COMMAND][4][3]
Start a remote programming software (RPS) session
when the phone rings at the control panel.
L## Move to Area
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
30
Move to Area
[COMMAND][5][0]
Temporarily switch to a different area and perform
keypad functions related to that area.
L## Display Rev
Default:
Refer to the program record sheet
Selection:
- or E
Function
No.
Function Name
Alternate
Keystroke
32
Display Software
Revision
[COMMAND][5][9]
Display the control panel model name and software
revision. For example:
7212GV3 REV ##.##
L## Service Walk
Default:
Refer to the program record sheet
Selection:
- or E
Function No.
Function Name
Alternate Keystroke
33
Service Walk Test
(Menu function only)
Start a Service Walk Test for all 24-hour Interior or
Perimeter Controlled points in the control panel.
Points are not included in this test if:
Points are in an area that is already in a Walk
Test Mode.
Points are assigned to an area that is not
enabled
A# Area On
.
Points are in an area that is Master or
Perimeter armed.
When a Service Walk Test is initiated, one person
can test all the points in the control panel without
assistance. The following features are provided with
the Service Walk Test:
Display indicates exactly how many points
can be tested.
Battery and bell tests do not occur during this
Walk Test.
The test ends when all points are tested or
the test times out after 20 min of inactivity.
Events print locally without alarm
annunciation or reporting to the central
station receiver.
D1255 Keypad displays a sequential count
and the text for the point after each point is
activated and restored.
The D1255 Keypad displays
ALL PNTS
TESTED
.
If enabled in Routing, Service Start and
Service End are reported at the central
station receiver for the beginning and end of
the test.
Point 128 appears as missing. This is normal. This
points is used for supervising the Zonex 1 bus (Point
128). If the Zonex bus has a fault, these points
indicate a short.
This function allows viewing of extra points. Extra
points occur under two conditions: an extra point is
wired electrically to the Zonex bus with
### Point
Index
set to
0
, or two Zonex devices exist for the
same Zonex address.