Schedules (Skeds)

 

EN 

| 108 

 

 

Bosch Security Systems, Inc. | 10/11 | F01U170808-02 

 

Default: 

Selection: 

0 to 24, 28, 29 

13 

Adjust Time Forward One Hour: This sked function is used to make adjustments to the control 
panel’s clock. A typical application is to program this to go into effect at 2:00 AM on the date 
that Daylight Saving Time begins (during the springtime). No Time Change Report is sent or 
logged, but the new time appears in the next report logged. 

No other parameters require input for this option. 

14 

Adjust Time Backward One Hour:

 This sked function is used to make adjustments to the control 

panel’s clock. A typical application is to program this to go into effect at 2:00 AM on the date that 
Daylight Saving Time ends (during the fall). This function can operate only once in a day, even if 
multiple Skeds with this function are programmed. No Time Change Report is sent or logged, but the 
new time appears in the next report logged. 

There are no other parameters that require input for this option. 

   

 

 

S## Cmd Center 1[through 8] 

 

15 

Sound Watch Tone at 
Command Center

 (Keypad): This 

function sounds the Watch Tone 
at the keypad address 
programmed in Parameter 1. The 
Watch Tone sounds at all 
keypads with the address 
programmed. Press [ESC] to 
silence the tone. 
Sound Watch Tone defines the 
keypad address where the Watch 
Tone sounds. Enter the specific 
address at the 

S## Cmd Center

 

prompt. 

Default: Blank 
Selection: Yes or No

 

Enable the sked to beep the keypad 
programmed 

Yes

Yes 

 

Watch tone 
sounds at this 
keypad. 
 

28 

Expanded Off-Normal Test Report:

 To generate this event, one or more points must be in an off-

normal state at the time the sked executes. In addition, any system trouble that is active also 
generates an Expanded Off-Normal Test Report. Expanded Off-Normal Test Reports include the Off 
Normal Test Report Event as well as the supplementary event at the time the report is generated. 

The Event Log shows only a Test Report Event. 

If none of these conditions exists at the time the sked executes, only a Sked Executed Event is 
generated and the Off-Normal Test Report is not sent. 

29 

Non-Expanded Off-Normal Test Report:

 Non-Expanded Off-Normal Test Report Events are only 

sent when any point is in the off-normal state from any area, but only sends the Off Normal Test 
Report Event. Any system trouble that is active also generates a Non-Expanded Off-Normal Test 
Report. 

The Event Log only shows a Test Report Event. 

If none of these conditions exist at the time the sked executes, only a Sked Executed Event is 
generated and the Non-Expanded Off-Normal Test Report is not sent. 

 

 

To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use 
Sked Function Code 9, Test Report and program it to occur on a daily basis as per AHJ 
requirements. 

 

 

 

 

 
 
 

Содержание D7212GV3

Страница 1: ...EN Program Entry Guide Control Panel D7212GV3 v8 11 and Higher ...

Страница 2: ... Type Styles Used in this Manual To help identify important items in the text the following type styles are used Prompt A thick border is used to indicate a main programming entry as seen in the Remote Programmer s Display It is used as a section heading and screen example Shaded boxes indicate programmer prompts that are only available when Custom or View events are selected Sub Prompt A dashed b...

Страница 3: ...s Control Functions 57 2 10 4 Custom Functions 60 2 10 5 Configuration Authority 60 Keypad Programming of the Keypad Programming Option 61 2 10 6 Authority Level Selections 61 General Functions 64 2 10 8 Access Control Levels 68 2 10 9 SIA Duress Passcode Options 68 2 11 Function List 69 2 12 Relay Parameters 69 2 12 1 Area Relays 70 2 12 2 Panel Wide Relays 72 3 0 Passcodes Access Credentials and...

Страница 4: ...t Reports 18 Table 10 Diagnostic Reports 19 Table 11 Relay Reports 19 Table 12 Auto Function Reports 20 Table 13 RPS Reports 20 Table 14 Point Reports 20 Table 15 User Change Reports 21 Table 16 Access Reports 21 Table 17 Event Descriptions Priorities and Numbers 22 Table 18 Verify Time 33 Table 19 CF Key Strokes 52 Table 20 CF Custom Function Keystrokes 53 Table 21 Keypad Programming Choices 55 T...

Страница 5: ...259 1 2 Guide to Programming Options Full configuration of the control panel is only achieved through use of the Remote Programming Software RPS A limited keypad programmer s mode is available to modify some of the more commonly changed parameters This guide is set up in a specific order Related program entries are grouped together in modules as they appear in RPS The Program Item Prompt Each prom...

Страница 6: ...uration Authority on page 60 and all control panel areas must be disarmed Figure 1 D1255 Keypad Programming Menu and Page References Refer to Phone on page 8 Refer to Phone Format on page 9 Refer to Enhanced Comm on page 117 Refer to R Primary Device on page 14 and R Backup Device on page 15 Refer to RPS Passcode on page 27 Refer to RPS Phone on page 29 Refer to RPS IP Address on page 115 Refer to...

Страница 7: ... 25 Refer to RPS Phone on page 29 Refer to RPS IP Address on page 115 Refer to RPS Port Number on page 116 Refer to A Area On on page 31 and A Account Number on page 31 Refer to CC Scope on page 47 and CC Enhanced Command Center on page 49 Refer to P Point Index on page 91 Refer to R Primary Device on page 14 and R Backup Device on page 15 Refer to Enhanced Comm on page 117 Refer to 2 10 5 Configu...

Страница 8: ...ore the phone number The control panel waits 2 sec and does not wait for the dial tone break The control panel is programmed with a seven sec dial tone detect period When a dial tone is detected or the waiting period ends the control panel begins to dial To extend the dial tone detect period place a D before the phone number To insert a pause during or after dialing use C in the number sequence Fo...

Страница 9: ...and ENTER keys on the keypad to enter the new phone number 5 Press the Save softkey When the keypad reads Parameter Saved your selection has been configured 2 2 Phone Parameters The program items in this category describe panel wide characteristics for telephone dialing receiver format and supervision Phone Format Default Modem IIIa2 Selection Modem IIIa2 or Contact ID Modem IIIa2 Modem IIIa2 Comm...

Страница 10: ...ation data files are not set up for point and User ID number reporting you can use this program item to convert these numbers to COMEX Reports When Phone Format is Yes the control panel sends expanded Bosch Modem IIIa2 Communication Format Reports to the receiver Point User Flag affects Bosch Modem IIIa2 Communication Format data as shown in Table 2 The Bosch Security Systems Inc D6600 Receiver ad...

Страница 11: ...and CC Trouble Tone is Yes Phone Trouble and Restoral Events report when they occur They report also when a Diagnostic Report is initiated from a keypad or by a Sked Alarm On Fail Default No Selection Yes or No Yes Generate alarm responses when a phone line fails No Phone failures report as trouble responses for Area 1 or the account number associated with Area 1 Phone Supv Time must be programmed...

Страница 12: ...1 Called Party Disconnect Telephone companies provide called party disconnect to allow the called party to terminate a call The called party must go on hook hang up for a fixed interval before a dial tone is available for a new call This interval varies with telephone company equipment D7212GV3 firmware allows for called party disconnect by adding a 35 sec on hook interval to the dial tone detect ...

Страница 13: ...g on page 12 1 Select Route Group 1 2 Program a SDI 88 Path 1 for RG1 Primary Destination 3 Program a Phone 1 for RG1 Backup Destination 4 Enable all applicable events to be included in Route Group 1 Phone Refer to Section 2 1 Phone on page 8 1 Select Phone 1 2 Program Phone 1 with the applicable central station receiver phone number AUXPARM Refer to Section 6 6Programming Path Numbers and IP Addr...

Страница 14: ...fault No Device Selection No Device Phone 1 4 SDI Path 1 4 No Device This route group is disabled Phone 1 Phone 1 is this group s primary destination Phone 2 Phone 2 is this group s primary destination Phone 3 Phone 3 is this group s primary destination Phone 4 Phone 4 is this group s primary destination SDI 88 Path 1 Path 1 on SDI 88 is this group s primary destination SDI 88 Path 2 Path 2 on SDI...

Страница 15: ... Device This route group is disabled Phone 1 Phone 1 or SDI Path 1 is this group s backup destination if the primary destination fails Phone 2 Phone 2 or SDI Path 2 is this group s backup destination if the primary destination fails Phone 3 Phone 3 or SDI Path 3 is this group s backup destination if the primary destination fails Phone 4 Phone 4 or SDI Path 4 is this group s backup destination if t...

Страница 16: ...Route Group 1 4 option 2 At the Route Group 1 4 prompt enter the route group number you wish to configure and press ENT The keypad reads Rt Group 1 Primary and then the current configuration for example SDI 88 PATH 4 3 Press the Backup softkey The keypad reads Rt Group 1 Primary and then the current configuration for example SDI 88 PATH 4 The Primary device cannot be set to No Device before settin...

Страница 17: ...s Point Time elapses R Unverified Evt encompasses both Fire and Non fire points but is not related to the A Verify Time used for smoke detectors The D7212GV3 logs a Ground Fault Event as Trouble Point 256 Restoral Reports are not sent if the control panel resets after a point is bypassed and then unbypassed This is true for both Fire and Non fire points User Reports Selecting Yes enables a report ...

Страница 18: ...enable Sked Function Code 10 in the Skeds section of the program Manual To send a Status Report manually that includes the events shown in the footnotes in Table 9 enter COMMAND 4 2 at the keypad Refer to the Send Report prompt on page 57 Sending off normal conditions as a Status Report following a Test Report is required by some automation systems Sending off normal conditions as a Non status Rep...

Страница 19: ...Battery Low 1 Yes No Low battery power R Battery Rstl Yes No Restoral of battery power to control panel after Missing or Low Event R Rt Comm Fail 1 2 Yes No Failure to send report to specific route R Rt Comm Rstl Yes No Restoral of communication to specific route after a failure Table 10 Diagnostic Reports continued R Checksum Fail Yes No Checksum Fail Event R Network Fail 3 Yes No Failure of netw...

Страница 20: ...eshold Yes No Event log threshold reached R Log Overflow Yes No Log is full old events are overwritten R Para Changed Yes No RPS Parameter Change Event R RPS OK Yes No Successful RPS Access Event R RPS Fail Yes No Failed Access RPS Event R Remote Reset Yes No Remote Reset Event R Program OK Yes No Successful Local Programming Event R Program Fail Yes No Failed Local Programming Event Point Reports...

Страница 21: ...ontrol panel always uses the account number from Area 1 2 This event is not transmitted for the D7212GV3 Use only the default setting Access Reports Selecting Yes enables a report to be sent when the event occurs Access Reporting is not available with the D7212GV3 Table 16 Access Reports Report Selection s Report Description R Access Granted 1 Yes No Access Granted Event R No Entry 1 Yes No No Ent...

Страница 22: ... 050 Table 17 Event Descriptions Priorities and Numbers continued Event Description Event Priority Event Number Forced Close Perimeter Instant 007 084 Forced Close Perimeter Delay 007 085 Perimeter Instant Armed 008 088 Perimeter Delay Armed 008 089 Send User Text n a n a S Alarm n a n a S Trouble n a n a S Supervision n a n a Status Report 008 035 S Open n a n a S Close n a n a Test Report 008 05...

Страница 23: ...wer must be off before the control panel responds to the AC failure The response to restoral of AC power is delayed for the same amount of time The control panel always monitors AC The response to this prompt is the actuation of the relay programmed in the Panel Wide Relays prompt AC Failure refer to Section 2 12 2 Panel Wide Relays on page 72 and the AC Fail report enabled by the AC Fail Restoral...

Страница 24: ... program AC Fail Restoral Report as No if AC Tag Along is programmed Yes AC Battery Buzz Default No Selection Yes or No Yes Initiates panel wide trouble tone at all keypads No Does not initiate panel wide trouble tone at keypads Initiates a panel wide trouble tone at keypads when AC fails or battery is low or missing This program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays T...

Страница 25: ...SDI Reports for the printer if the D9131A becomes disconnected P Scope Default No Printer Selection No Printer Area Account Panel Wide Custom Panel Wide Printer prints all designated events that occur panel wide A panel wide printer can cross account boundaries Account Printer prints all designated events that occur within any area with the same account number in which this printer is assigned Are...

Страница 26: ...porting format when RPS contacts the control panel and the passcode is incorrect the control panel sends an RPS Access Fail Report to the central station receiver RPS Access Fail also occurs when the call is not terminated with either a Good bye or Reset bye command RPS ACCESS OK is sent according to phone routing when a Good bye command is entered from RPS to terminate the call When a Reset bye i...

Страница 27: ...ode Keypad Programming of RPS Passcode D1255 1 Refer to Figure 1 on page 6 to access Keypad Programming and navigate to the RPS PASSCODE option The keypad shows the currently configured passcode 2 Press ENT to change the passcode An editing cursor is enabled 3 The PREV button acts as a Backspace key The COMMAND key allows you to cycle though the special passcode characters A B C D E F the NEXT key...

Страница 28: ... the control panel hears the correct RPS passcode it hangs up the phone seizes the phone line then dials the programmed RPS phone number refer to the RPS Ph prompt in this section This ensures that the control panel only communicates with RPS units connected to the programmed phone number If the call is answered manually the call back must be initiated manually No The RPS session starts immediatel...

Страница 29: ...erimeter armed a disarmed state RPS Phone Default Blank Selection Blank or up to 24 characters Blank Control panel does not dial a phone number for RPS 1 to 24 characters Enter up to 24 characters to define dialing characteristics This is the phone number the control panel dials to contact RPS The control panel dials the programmed number on Phone 5 RPS Ph The control panel dials this number when ...

Страница 30: ...el communication when using a PSTN connection 2 7 Miscellaneous Duress Type Default 0 Selection 0 1 2 or 3 0 Do not send a duress event with any passcode 1 Increase the last digit by 1 to generate an alarm For example if the passcode is 6123 6124 activates a duress alarm If the last digit of the passcode is 0 a duress alarm occurs when the user enters 1 as the last digit of the passcode If the las...

Страница 31: ...Default 0000 Selection For Modem or Contact ID four digit account numbers 0000 to 9999 BBBB to FFFF For Modem ten digit account numbers 0000000000 to 9999999999 BBBBBBBBBB to FFFFFFFFFF Determines the account number for this area An account number must be assigned to each active area Account numbers are used to group areas together Each area can have a different account number or several areas can...

Страница 32: ...points that can be faulted or bypassed when arming this area Refer to the prompts P Force Arm Returnable and P Bypass Returnable in Section 4 2 Point Responses on page 81 for returning a point to the system when the point returns to normal or when the area is disarmed Users can bypass more points than the number entered here during the disarmed state It is only when the user attempts to Bypass Arm...

Страница 33: ...n alarm occurs Example Verify Time is set for 20 sec The alarm verification cycle starts when the detector senses smoke or fire No report occurs When the detector senses smoke or fire the area s sensor reset relay interrupts power to points connected to it for the time in Verify Time When power restores to the points the 60 sec confirmation window starts If any detector reset during the verificati...

Страница 34: ...nt Wide all associate areas enters exit delay as soon as the master area is armed If there is a shared area within the same account it begins its exit delay after all associate areas are armed Using the arming sked S Function 1 requires that you first use an arming sked to arm the associate areas before using an arming sked to arm the master area Arming master areas with RPS Keyswitch or Auto Clos...

Страница 35: ...n the Shared Area Silence shared area alarms and troubles from any keypad To silence sounders the user needs an authority level assigned to the shared area If the user also has the authority to arm or disarm the area then ALREADY ARMED or ALREADY DISARMED momentarily appears Closing Reports for Shared Areas If Closing Reports for shared areas are needed assign passcodes a valid authority level in ...

Страница 36: ...s the bell rings for Burglary Alarm points The relay activated for this time is programmed in A Alarm Bell in Area Relays The bell output begins as soon as the burglary alarm occurs It shuts off the bell when the programmed number of minutes expires When the control panel s internal clock begins a new minute it considers the first minute expired Program Burg Time for two min or more Check with you...

Страница 37: ...imultaneously and report to the central station the Bell Test occurs as the central station receiver confirms each area 2 8 4 Open Close Options Programming determines if Opening All Normal Closing and Force Arm Bypass Closing Events are sent to the remote central station Without remote reports all control panel and area arming Closing Events and disarming Opening Events default to local events Us...

Страница 38: ...the A Account O C feature To use these features program O C Windows A Account O C Default No Selection Yes or No Yes Send Opening and Closing Reports by account Use this selection if the control panel sends reports to an automation system that cannot interpret multiple Area Opening and Closing Reports An Account Opening Report is generated when the first area in an account is opened disarmed After...

Страница 39: ...dow If an opening or closing occurs outside of the appropriate window it reports but does not have an early or late modifier If you want to monitor all opening and closing activity and use features provided by Opening and Closing Windows program this item as No and program the appropriate O C Windows Determines if opening and closing activity is reported when it occurs inside an Opening or Closing...

Страница 40: ...nd this item is Yes the area sends only Restricted Opening and Closing Reports In this case Restricted Reports are sent without User ID Opening Closing Window does not affect this report Windows do not prevent sending Restricted Opening and Closing Reports from being sent Early or late designations are not added to Opening or Closing Reports when they are sent according to the rules for Restricted...

Страница 41: ...efault entry of 00 00 disables the Latest Close Time feature for this area The control panel sets all windows for the next day when the control panel clock turns to midnight The control panel must cross the midnight boundary before any changes in that default setting occur To extend across midnight you must use two windows To suppress reports before midnight use one window for example 20 00 start ...

Страница 42: ...s NO AUTHORITY and returns to idle text or entry delay D1260 Keypad In the D1260 after the first valid passcode is entered the following message appears for three sec Then the next message appears requesting a second code When the first digit of the second code is pressed the following message appears As each digit is pressed an additional asterisk appears A Early Ambush Default No Selection Yes o...

Страница 43: ...is feature activates when a controlled point with delay alarm response changes from normal to faulted and back to normal during the exit delay When activated if any controlled point in the same area with delay alarm response is faulted the exit delay time restarts The exit delay continues until it expires or the area changes arming states This operation can occur only once in an arming cycle To av...

Страница 44: ... section contains three programming categories Cmd Cntr Assignment Area Text and Custom Function 2 9 1 Keypad Command Center Assignment This programming category assigns a keypad to an area and determines if the keypad is supervised The keypads are connected to the control panel using a two wire serial data interface SDI bus This bus can support up to eight supervised keypads each with its own uni...

Страница 45: ... 1 Selection 1 to 8 DIP Switch Setting SDI CC 1 2 3 4 5 6 1 ON ON ON ON ON 2 OFF ON ON ON ON 3 ON OFF ON ON ON 4 OFF OFF ON ON ON 5 ON ON OFF ON ON 6 OFF ON OFF ON ON 7 ON OFF OFF ON ON 8 OFF OFF OFF ON ON Enter the keypad CC number for the SDI address you are programming This number corresponds to the DIP switch address settings shown ...

Страница 46: ...CC NUM 1 16 option shows 3 Enter the keypad number you wish to configure and press ENT The keypad reads CC SCOPE and then the current configuration for example PANEL WIDE 4 Press NEXT The current keypad type shows for example CC 1 TYPE ENHANCED YES 5 Press ENT to change the keypad s type 6 Press NEXT or PREV to toggle to No to indicate that the D1255 is not an enhanced keypad and then press ENT to...

Страница 47: ...settings for the custom parameters in CC A1 through A4 in Scope Before exiting a custom program check each area and ensure that it is enabled and disabled correctly CC A1 through A4 in Scope Default Refer to the preceding important note Selection Yes or No Yes Include this area in the scope of this keypad No Do not include this area in the scope of this keypad Determines whether any of the four ar...

Страница 48: ...lt No Selection Yes or No This feature is not available with the D7212GV3 Keep the default setting CC Assign Door Default Blank Selection 1 to 8 Blank This feature is not available with the D7212GV3 Keep the default setting CC Trouble Tone Default Yes Selection Yes or No Yes Panel wide trouble tones sound and visual displays show at this keypad No Panel wide troubles do not sound Visual displays s...

Страница 49: ...ed at this keypad address this item must be set to Yes Reboot the system to enable a D1260 Series keypad To reboot the system close and open the reset switch labeled S1 RESET located in the upper right corner of the control panel CC Passcode Follows Scope Default Yes Selection Yes or No Yes Master Arming allows a user to change the armed state of the areas within the scope of this keypad If the ar...

Страница 50: ...r s authority level Determines if the Menu Key when pressed requires a passcode to access the functions If this parameter is set to Yes users must enter a passcode after pressing the Menu key When the passcode is validated only those functions for which the user has authority appear in the list If a function in the Menu List is passcode protected refer to Keypad Functions in Section 2 11 2 User In...

Страница 51: ...A IS ON text instead of the ACCT IS ON text Unique ACCT IS ON Text Each area can have unique ACCT IS ON text or you can program the same text in each area of the account so when all the areas in the account are armed they all show the same text D1260 Series Keypad Although it is not programmed in this area the D1260 Series Keypad can display up to sixteen characters for an Area Name on line 1 of i...

Страница 52: ...valid character entries Determines the menu text displayed at the keypad for the custom function item Use this text to represent the functions performed by this menu item CF Key Strokes Table 19 CF Key Strokes Default Selection Refer to the program record sheet Up to 32 characters 0 to 9 A B C D E Selection D1255 Key D1255 Faceplate Label D1260 Key 0 to 9 0 to 9 0 to 9 A COMMAND COMMAND B PREV pre...

Страница 53: ...tion from the menu list ENTER PASSCODE or Enter Passcode Enter Key on the D1260 appears when this function is passcode protected If a command within the Custom Function is passcode protected ENTER PASSCODE appears at the keypad The user must enter a valid passcode must be entered before proceeding with the rest of the Custom Function If a passcode is not entered within 10 sec the Custom Function t...

Страница 54: ... is assigned based on the authority level assigned to the user s passcode for that area When the passcode is entered at the keypad the control panel checks the authority level The control panel executes the function only in areas where the passcode has the authority to use the function 2 10 1 Commands Similar to command initiation used in other Bosch Security Systems Inc products the Commands meth...

Страница 55: ...evel Function No Function Name Alternate Keystroke 2 Master Arm Delay COMMAND 1 Use this arming function to master arm disarmed areas If enabled the following arming choices are available to the user with this authority Master Arm Instant Default Disabled Selection E or P Function No Function Name Alternate Keystroke 3 Master Arm Instant COMMAND 1 1 Use this arming function to master arm instant a...

Страница 56: ...l ignores the A Force Arm Bypass Max entry in Section 2 8 Area Parameters on page 31 Local Only Reporting No Closing Report is sent to the central station but a Perimeter Delay Closing Event is generated in the event log View Area Stat Default P Selection E or P Function No Function Name Alternate Keystroke 8 View Area Status Menu function only Use this function to view the armed status of all are...

Страница 57: ...t P Selection E or P This feature is not available with the D7212GV3 Keep the default setting Access Ctl Level Default P Selection E or P This feature is not available with the D7212GV3 Keep the default setting Change Display Default E Selection E or P Function No Function Name Alternate Keystroke 15 Change Display COMMAND 4 9 Use this function to select either a bright or dim display with loud or...

Страница 58: ...arly Begin time passes and the Closing Window is active View Log Default E Selection E or P Function No Function Name Alternate Keystroke 21 View Log Menu function only Use this function to view all of the system events their time stamps User IDs or point numbers User Name and Point Text are not stored in the event log but they appear when the control panel matches them with the User ID and the Po...

Страница 59: ...nbypassed Reset Sensors Default E Selection E or P Function No Function Name Alternate Keystroke 27 Reset Sensors COMMAND 4 7 Use this function to activate the Reset Sensors function for Fire or Intrusion points programmed as P Resettable in Section 4 1 Point Index on page 77 Points within the scope of the keypad where the function is entered reset Refer to Section 2 9 1 Keypad Command Center Assi...

Страница 60: ...ion Name Alternate Keystroke 36 Invisible Walk Test Menu function only This function allows a user with the L Invisible Walk Test authority to test invisible interior or perimeter controlled points that are within the scope of the keypad without sending reports to the central station Invisible points must have the P Invisible Point function programmed Yes 2 10 4 Custom Functions C Function 128 thr...

Страница 61: ...n 2 10 6 Authority Level Selections on page 61 to determine which Authority Level can access keypad functions that are passcode protected Selecting Enable items in the Authority Level section is not necessary if the keypad function is disabled or enabled Each individual function has two selections you can use for the authority level you are programming Table 22 Authority Level Selections Authority...

Страница 62: ...here the keypad is assigned Use COMMAND 11 carefully because all Perimeter and Interior points become Instant Armed L Perimeter Instant Default Refer to the program record sheet Selection or E Function No Function Name Alternate Keystroke 4 Perimeter Instant Arm COMMAND 2 Instant arm all Perimeter points including Delayed points only in the area where the keypad is assigned L Perimeter Delay Defau...

Страница 63: ...he Walk Test starts The test ends when all points are tested or the test times out after 20 min of no activity Local alarm annunciation and event printing no reports are sent to the central station receiver D1255 Keypad displays a sequential count and text after each point is activated and restored The keypad displays ALL PTS TESTED and an All Points Tested Event is sent to the central station rec...

Страница 64: ...the D7212GV3 Keep the default setting L Secure Door Default Refer to the program record sheet Selection or E This feature is not available with the D7212GV3 Keep the default setting L Access Control Level Default Refer to the program record sheet Selection or E This feature is not available with the D7212GV3 Keep the default setting General Functions L Change Display Default Refer to the program r...

Страница 65: ...r E Function No Function Name Alternate Keystroke 22 Print Event Log Menu function only Print all panel wide events from the log to the printer in the area where the user is executing this function This item can also be accessed using the Service Menu 9 9 ENT L User Cmd 7 Default Refer to the program record sheet Selection or E Function No Function Name Alternate Keystroke 23 User Command 7 COMMAN...

Страница 66: ... Alternate Keystroke 33 Service Walk Test Menu function only Start a Service Walk Test for all 24 hour Interior or Perimeter Controlled points in the control panel Points are not included in this test if Points are in an area that is already in a Walk Test Mode Points are assigned to an area that is not enabled A Area On Points are in an area that is Master or Perimeter armed When a Service Walk T...

Страница 67: ...person can test invisible points without assistance The following features are provided with the Invisible Test Mode The display indicates exactly how many invisible points are assigned to the area Battery and bell tests do not occur during this walk test The keypad shows point text when invisible points are tested The test ends when all points are tested or if the test times out after ten min of ...

Страница 68: ...rity Level Default Refer to the program record sheet Selection M P D or This feature is not available with the D7212GV3 Keep the default setting L Disarm Level Default Refer to the program record sheet Selection I D or This feature is not available with the D7212GV3 Keep the default setting L Function Level Default Refer to the program record sheet Selection M D C or This feature is not available ...

Страница 69: ...Default Refer to the program record sheet Selection Yes or No Yes This menu item appears at this keypad address No This menu item does not appear at this keypad address Programming this prompt determines at which CC address setting this menu item appears 2 12 Relay Parameters Relays provide dry contact normally open or normally closed outputs for LED annunciation and other applications as well as ...

Страница 70: ...st be manually set to the correct state using the Change Relay Function COMMAND 54 Relay functions that resume the proper state within one min Alarm Bell Perimeter Fault Summary Fire Summary Trouble Area Armed Reset Sensors Fire Bell AC Fail Summary AlarmPhone Fail Silent Alarm Summary SupBurg Area Fault Battery Trouble Summary Fire Trouble Communications Fail Watch Mode Summary SupFire Relay func...

Страница 71: ...ns active until the area disarms or the control panel resets If Force Bypassing is required during Perimeter Arming this relay does not activate A Watch Mode Default 0 Selection 0 1 to 24 A B or C This relay activates when a Controlled point programmed for P Watch Point is faulted in the specified area while the area is in Watch Mode and the point is not armed It remains active for 2 sec after eac...

Страница 72: ...lly resets when battery power restores Use this relay to create audible annunciation Enable the keypad s trouble sounders for all applications except commercial fire systems Phone Fail Default 0 Selection 0 1 to 24 A B or C Activates when a telephone line failure occurs A time must be entered in Ph Supv Time refer to Section 2 2 Phone Parameters on page 9 for this relay to activate This relay rese...

Страница 73: ...any Fire Supervisory point in the control panel is in a supervisory condition off normal This relay provides a steady output until all Fire Supervisory points are restored to a normal condition Summary Trouble Default 0 Selection 0 1 to 24 A B or C Activates when any Non fire point in the control panel is in a trouble condition This relay provides a steady output until the user at the keypad ackno...

Страница 74: ... passcode tamper condition is also reported in a manually initiated Extended Test Report and to RPS through control panel diagnostics As a result the tamper condition is reset after the successful completion of a manual report or when disconnecting from an RPS session The tamper condition is not reset when the control panel reboots 3 1 3 User Group Window Use U User Group to enable and disable the...

Страница 75: ...e User 000 When a user other than User 000 tries to delete the passcode for User 000 the keypad displays NOT IN USE User 000 cannot be added or changed at the keypad whether it exists or not U Passcode Default Refer to the program record sheet Selection Three to six digits 0 to 9 Enter three to six digits to enable a passcode for the master user in this group User I D 000 is the reserved user for ...

Страница 76: ...mote programming software RPS U Area 1 through Area 4 Auth Default Refer to the program record sheet Selection 0 to 14 Assign an authority level to the user for this area A setting of 0 means the user has no authority in this area U Name Default Refer to the program record sheet Selection Sixteen alphanumeric characters Enter Alphabetic characters A to Z in capital letters Period comma percent par...

Страница 77: ...hour point consider using a Perimeter point type with a Point Response of 9 to E 24 hour points do not show faults when an arming function is entered but Perimeter points do When programming this type of protection consider also using the Buzz on Fault and Local While Disarmed options 1 Perimeter Perimeter points are armed with all arming functions Points programmed as perimeter can also be armed ...

Страница 78: ...oint s entry delay time is less than the remaining time it shortens the entry delay time Delayed points can also activate an entry tone at the keypad refer to the P Ent Tone Off prompt in Section 4 2 Point Responses on page 81 In some cases you might need to create an Interior point that causes an instant alarm if the entry delay is not started first Use Interior Follower to create this type of pr...

Страница 79: ...isarming Point Response must be programmed 1 Do not connect initiating devices to a Keyswitch point N S N When this point momentarily changes from normal to shorted to normal it toggles the armed state of the area Open An open is a trouble while the point is disarmed An open is an alarm while the point is armed When this point changes from open to normal it restores 5 Trouble and Restoral Reports ...

Страница 80: ...grammed in Area Parameters and to provide bell control If the D279 s W1 jumper is closed no Area Open or Area Close Report is sent and alarm bells can only be silenced from a keypad no matter how the control panel is programmed Normal When this point changes from open to normal the area arms Open The area is disarmed The alarm bell silences if an alarm occurred while the area was armed 8 Short A s...

Страница 81: ...cs of a Fire Point Reporting When a group of events occurs the control panel routes and prints out Fire Reports first Visual Annunciation FIRE TROUBLES continues to scroll until the trouble clears When acknowledged a FIRE TROUBLE scroll notifies the end user that a Fire point or group of Fire points is still in trouble Panel Wide Relays Summary Fire and Summary Fire Trouble activate if a relay is ...

Страница 82: ...T I I T I T Disarmed Short T T T I T I I 24 Hour Points Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F Open I T I T I T S T S S Short I I T T I T T S S S Key I Instant alarm D Delayed alarm T Trouble S Supervisory Blank Audible or visual response Example of Controlled point Point Type 1 Point Response 8 Perimeter point with delayed alarm response when armed opened or shorted and no response when d...

Страница 83: ...ntry delay starts If an interior point must fault during entry delay to allow the user to disarm the area at a keypad program P Type as 3 Interior Follower For SIA CP 01 Compliance P Entry Delay must be between 30 sec and 240 sec P Entry Tone Off Default No Selection Yes or No Yes Disables the entry delay tone when this perimeter point is faulted This is intended for use with points set to P Type ...

Страница 84: ... failed attempts No P Silent points do not cause the A Burg Alarm relay to activate even if the report does not get to the central station receiver When set to Yes if the report fails to reach the central station after two attempts a silent alarm rings the A Burg Alarm bell A silent alarm is generated when a point with P Silent set to Yes is faulted while armed When a point programmed for P Silent...

Страница 85: ...e normal before the user can silence the buzz 3 The point buzzes at the keypad for any fault condition when the area is disarmed The user cannot silence this buzz but it silences automatically when the point is restored If the fault condition results in a trouble response the keypad continues to buzz even after the user acknowledges the condition if the fault is still present The point buzzes at t...

Страница 86: ...ed relay Relays are not available for Points 25 to 40 Do not use the Change Relays function to toggle relays reserved for special functions Special function relays are Area and Panel Wide Relay functions as well as relays assigned to CC Enter Key Relay and P Relay Response Type P Display as Device Default No Selection Yes or No Yes Display CHECK DEVICE when this point is off normal No Do not displ...

Страница 87: ...fect local annunciation Local While Armed suppresses all reports from 24 hour points Do not use P Type 0 for this prompt This setting works only for disarmed points Type 0 is a 24 hour always armed point Choose any Type other than 0 and use a point response that reports an alarm whether or not the point is armed For instance P Type 1 and P Response 9 reports an alarm on a trouble or a short whethe...

Страница 88: ...s bypassed 24 HOUR BYPASS scrolls continuously at the keypad 24 HOUR BYPASS scrolls to indicate that a 24 hour Non fire point P Fire No is bypassed FIRE BYPASS scrolls to indicate that a 24 hour Fire point or a Fire Supervisory point is bypassed Alternative to a 24 hour Point For alarm capability of a 24 hour point without the continuous scrolling use a Perimeter point with a Point Response of 9 t...

Страница 89: ...ccurring until the area is armed When the area is armed the bypassed points and any point being bypassed during the arming sequence report as POINT BYPASS along with the Closing Report When P Defer Bypass Report is set to Yes and Closing Reports are suppressed by using Closing Windows the deferred Bypass Reports are not sent Bypass Reports for 24 hour points do not report If P Report Bypass at Occ...

Страница 90: ... 5 sec The time programmed in A Verify Time is ignored P Resettable Default Refer to the program record sheet Selection Yes or No Yes This point is reset by the Reset Sensor Function and during the alarm verification sequence No This point is not resettable Use this option if this is a Powered point that requires interruption of power to reset a latched alarm condition The Resettable point option ...

Страница 91: ... count Relay for assigning relays to follow alarms for a group of points and custom keypad and report text for each point Point Number Default 1 Selection to 40 Enter the point number you are programming When transmitting in Modem IIIa2 the three digit point number is reported to the central station receiver Point number 128 is reserved for supervising Zonex 1 P Point Index Default Refer to the pr...

Страница 92: ...5 The PREV button acts as a Backspace key Press PREV to delete the characters of the index number and then enter the new index number The keypad does not accept invalid index numbers 6 Press ENT to save the changes When the keypad reads PARAMETER SAVED your selection has been configured D1260 Press ENT to save the changes 1 Refer to Figure 2 on page 7 to access Keypad Programming and navigate to t...

Страница 93: ...et Selection Up to sixteen alphanumeric characters Enter alphabetic characters A to Z in capital letters Enter up to sixteen characters of text to describe the point This point text is shown at keypads if the point is programmed as visible and sent to the central station receiver when transmitting in Modem IIIa2 format if it is a reporting point Include the point number in custom point text This h...

Страница 94: ...ss normal Opening or Closing Reports when A Disable O C in Windows is programmed as Yes Generate a Fail to Open Report if the area is not disarmed on schedule when A Fail To Open is programmed as Yes Provide a warning tone and a PLEASE CLOSE NOW display at the keypad when it is time to arm the area Generate a Fail to Close Report if the area is not armed on schedule when A Fail To Close is program...

Страница 95: ...s one of three required to create an Opening Window To finish programming an Opening Window Open Window Start and Open Window Stop must be programmed The time programmed in the W Open Early Begin field is the earliest time that the user is allowed to open an area before the Opening Window Start time If Opening and Closing Reports are enabled disarming the area between midnight and the open Early B...

Страница 96: ...entered as 23 59 This program item is one of three required to create an Opening Window To program an Opening Window Open Early Begin and Open Window Stop must also be programmed Refer to the W Open Early Begin prompt on page 95 for explanations of report features W Open Window Stop Default 00 00 Selection HH MM hours and minutes Enter the time you want the control panel to end the Opening Window ...

Страница 97: ...If the area is not disarmed by 3 01 PM a Fail to Open Event is generated if Fail to Open is programmed Yes in Opening and Closing Options 9 If the user disarms the area between 3 01 PM and 11 59 PM a Late to Open Event is generated Table 26 Programming for Two Same Day Opening Windows refer to Figure 5 Open Close W Day of Week Early Begin Start Stop Early Begin Start Stop eXcept On Holiday Holiday...

Страница 98: ...is prompt is 00 00 but times are programmed for Close Window Start and Close Window Stop the window is disabled To disable the window both the hours and minutes spaces must be 00 00 00 00 is midnight 23 59 is 11 59 PM Make entries using a 24 hour clock for example 7 00 AM is entered as 07 00 2 45 PM is entered as 14 45 Reboot the control panel to activate today s window The window needs to activat...

Страница 99: ...t be later than the window start time To program a window that effectively crosses the midnight boundary you must program two windows For example to program windows for an area that closes between 11 30 PM and 12 30 AM five days a week use two windows as shown in Table 28 Table 28 Programming Example Using Two Closing Windows to Cross the Midnight Boundary Open Close W Day of Week Early Begin Star...

Страница 100: ...date is designated as a Holiday by the Holiday Index es selected Holiday Indexes for O C Windows You can enable up to four Holiday Indexes for use with Opening Closing Windows Enable at least one Holiday Index if W Xept Holiday is programmed as Yes for this window or if you want this window to activate only on specific dates Holidays are programmed in Section 5 3 Holiday Indexes on page 110 W Holi...

Страница 101: ... _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Yes No 1 2 3 4 1 2 3 4 5 6 7 8 Table 30 Opening and Closing Windows Day of Week The column below briefly describes how to activate an Opening Closing Window Use the guidelines shown in the other columns to choose the appropriate entries eXcept On Holiday Holiday Index Areas Program at least one day Yes Day s of the week No None Program at least one area...

Страница 102: ... 00 PM 5 1 2 User Group Windows In this section you can create up to eight User Group periods where the passcodes for the group chosen is enabled One user group can have multiple windows assigned to it over a 24 hour period Refer to the U User Group prompt in Section 3 1 Passcode or Token Worksheet to assign individuals to a group When you assign a U User Group to one of the eight windows all pass...

Страница 103: ...day when the window starts Beginning at this time users assigned to this window s group can use their passcodes The window goes into effect at the beginning of the minute Make entries using a 24 hour clock for example 7 00 AM is entered as 07 00 2 45 PM is entered as 14 45 If the window must activate on the same day that you program it reboot the control panel to activate it immediately UW Group D...

Страница 104: ...tion Code In addition to the function a choice must be made as to what is affected by the function For example when choosing Function 2 Disarm Sked the disarming is the function and the selected areas are what is affected The functions and their associated parameters are listed in the Sked Function Code Table in the D7212GV3 Program Record Sheet P N F01U003803 and they are explained in detail foll...

Страница 105: ...s sked bypasses The point can be bypassed only if Bypassable is programmed Yes in the point index assigned to the point The bypass is reported if the Bypass Reports is enabled by the point index settings assigned to the point The sked can bypass one point Default Blank Selections Blank 1 to 40 Enter the number of the point the sked bypasses Blank 0 1 to 40 No point is bypassed Point to bypass S Po...

Страница 106: ...d This is a panel wide function No other parameters require input for this option S Defer Test Yes Defer the Test Report Default No Selection Yes or No Enable sked to defer the Test Report No Send the Test Report on schedule S Hourly Report Yes Send the Test Report every hour 9 Test Report This function emulates the Test Report sub function of the Send Report keypad function COMMAND 4 1 This funct...

Страница 107: ...m function it is subject to the scope of the selected keypad Cmd Center and Custom Func prompts appear after entering Function Code 11 Both entries are required Selections Blank 0 128 to 131 for D7212GV3 Enter the custom function this sked executes 128 to 131 Custom Function to activate 12 Contact RPS This function attempts to contact an Unattended RPS at the configured time The control panel s ac...

Страница 108: ...e defines the keypad address where the Watch Tone sounds Enter the specific address at the S Cmd Center prompt Default Blank Selection Yes or No Enable the sked to beep the keypad programmed Yes Yes Watch tone sounds at this keypad 28 Expanded Off Normal Test Report To generate this event one or more points must be in an off normal state at the time the sked executes In addition any system trouble...

Страница 109: ...Holiday is programmed as Yes the window executes on the days of the week programmed unless the date is designated as a holiday by the Holiday Index selected If a sked is only needed on certain days of the year do not program the sked to execute on specific days of the week Instead program Xept Holiday as No and select a Holiday Index with the dates you want the window to be active S Monday Default...

Страница 110: ...ows and skeds Date Default _ _ _ _ Selection MM DD month and date This entry selects the month and day you are designating as a holiday To delete the date completely removed the Holiday setting by programming as No for all of the Holiday Index entries Holiday Index Default None Selection Select Dates from the Calendar Yes Use this date in Holiday Index 1 No Do not use this date in Holiday Index 1 ...

Страница 111: ...ross Point Parameters Route Group Parameters 6 3 SDI Automation SDI automation defines the characteristics of a serial interface module SIM when used with home or business automation software The SIM is a two way SDI to serial communication module that allows the control panels to send and receive information to and from an external software program The SIM can be a D9133 DX4010i or DX4020 configu...

Страница 112: ...issing AC Restore Battery Low and so on Relay status relay on or relay off Entries are in 100 msec increments If a 5 is entered the status information is sent every 500 msec or 0 5 sec An entry of 10 equals 1 sec 6 4 SDI RPS Parameters Configure remote programming software RPS parameters when communicating over a private local area network LAN wide area network WAN or general packet radio system G...

Страница 113: ...ule Provide enhanced route paths for event reporting through a network using a Conettix DX4020 Ethernet Network Interface Module Although not listed in this section RPS checks for the RPS passcode refer to Section 2 6 RPS Parameters on page 26 Datalock Code and control panel type to determine if this RPS session should continue The RPS via Phone prompt Figure 6 on page 114 if selected contacts RPS...

Страница 114: ...nter choice Use port 7700 Enter Port Number Exit rps via Port 7700 RPS connecting via phone via network Exit RPS connecting Exit Allow Answer or ringing Area Name area text Help Menu idle text Command key pressed System Command 43 pressed Enter choice RPS via Phone RPS via Network Exit Allow Answer Enter choice Enter Port Exit Enter Select Port rps via Port RPS via Network ...

Страница 115: ...dle text ENTER PORT ENT RPS IP Address Default 0 0 0 0 Selection 0 0 0 0 to 255 255 255 255 0 to 255 There are four numbers for an IP address Leading zeros are not required This prompt contains the IP address for RPS An IP address has four fields Each field has a range of 0 to 255 For example an IP address is expressed as 110 227 64 190 Contact your network administrator to determine the IP addres...

Страница 116: ...ete the characters of the port number and then enter the new port number 10 Press ENT to save the changes When the keypad reads PARAMETER SAVED your selection is configured D1260 1 Refer to Figure 2 on page 7 to access Keypad Programming and navigate to the RPS Parameters option Press ENT The keypad shows the RPS Passcode option and the currently configured passcode 2 Press Phone Number softkey Th...

Страница 117: ...vigate to the ENHANCED COMM option Press ENT 2 The keypad shows the current setting by alternating between COMMUNICATIONS and ENHANCED YES or NO To configure enhanced communications press ENT 3 Press NEXT or PREV to toggle to YES to enable enhanced communication or No to disable enhanced communication and then press ENT When the keypad reads PARAMETER SAVED your selection has been configured D1260...

Страница 118: ...o the central station receiver The value programmed in Path Ack Wait is the length of time the control panel waits for an acknowledgment of the Heartbeat Poll If the acknowledgment is not received the control panel checks to determine if the Path Retry Count entry is greater than 0 If so the control panel retries the number of times programmed in Path Retry Count to send the Heartbeat Poll before ...

Страница 119: ...ftkey to change the IP address An editing cursor is enabled for the first byte 5 The Previous and Next softkeys move the cursor through the bytes The Backspace softkey allows you to erase characters The Clear softkey allows you to clear the entire IP address Use the softkeys and the number buttons on the keypad to enter the new IP address The keypad does not accept invalid byte numbers 6 Press the...

Страница 120: ...anel handles them on a successive basis For example if acknowledgment from SDI Path 1 is not received within 10 sec using the previous example the control panel moves to SDI Path 2 to send its Heartbeat Poll and subsequently waits for the ack before returning to SDI Path 1 to re send its heartbeat If Heartbeat Polls are enabled to send by an SDI path and the Path Ack Wait time is exceeded a COMM T...

Страница 121: ...receiver Anti replay is a strategy that counters replay attacks This feature prevents a malicious attack that substitutes a control panel or another network interface module NIM from delivering counterfeit events over a network in place of events sent by the actual control panel A replay attack occurs when someone records a message sent over the network by Device A and replays this message at a la...

Страница 122: ...cation keys from the control panel to receiver are the same when the paths to the receiver use different IP Addresses or Port Numbers These parameters also enable the backup path poll time to change to the primary poll time in the event of a Communication Trouble condition This operates when the following conditions occur Both primary and backup devices use enhanced communication via an SDI device...

Страница 123: ...to continue or to stop after the Fire Alarm Bell is silenced or times out Refer to the Summary Fire prompt in Section 2 12 2 Panel Wide Relays on page 72 Fire Supervision Restoral Type Default 0 Selection 0 1 2 0 The control panel sends a FIRE TROUBLE RESTORE when a Fire Supervision point restores to normal 1 The control panel sends a FIRE ALARM RESTORE when a Fire Supervision point restores to no...

Страница 124: ... alarm silence operation is performed before this time elapses the alarm transmission is aborted and the keypad shows an optional ALARM NOT SENT message When an alarm transmission is successfully aborted no event is written to the control panel event log When an abort alarm timer starts it does not stop until an alarm silence operation is performed or the time expires This feature does not apply t...

Страница 125: ...bypassed For SIA CP 01 Compliance P Swinger Bypass can be Yes or No If P Swinger Bypass is Yes Swinger Count must be 1 or 2 Remote Warning Default Yes Selection Yes or No Yes The system uses the Alarm Bell output to annunciate the arming and disarming of an area through remote software or a remote arming device such as a key switch or key fob No No remote warning occurs to annunciate the arming an...

Страница 126: ...me called Cross Point Time from at least two points within a Cross Point Group Table 34 before Cross Point Alarm Events are generated These points must have P Cross Point set to Yes to generate this event There are five Cross Point Groups in the D7212GV3 Each Cross Point Group consists of eight points and is identified by the point numbers in them for example Cross Points 1 to 8 Cross Points 9 to ...

Страница 127: ...d for that point Conversely if a single Cross Point detects an alarm then restores and no other conditions occur an Unverified Event is generated for that point A second alarm on the first point does not create an Alarm Event but rather an Unverified Event Section 2 3 Routing on page 12 determines whether these events are transmitted to a central station An Unverified Event does not produce a corr...

Страница 128: ...in Page 36 A Alarm Bell 1 to 128 64 A B C A on board alarm output Page 70 CC Entry Tone Yes or No Yes Page 48 CC Exit Tone Yes or No Yes Page 49 CC Abort Display Yes or No Yes Page 50 CC Cancel Display Yes or No Yes Page 50 Master Arm Inst Blank Blank Page 55 Perimeter Instant Blank Blank Page 55 L Send Duress Blank or E E 2 Page 68 L Disarm Blank or E E 2 Page 61 L Passcode Disarm Blank or E E 2 ...

Страница 129: ...ter Parameters 25 Printer Address 25 P Area Assign 25 P Supervised 25 P Scope 25 P A1 through A4 in Scope 25 P Fire Events 25 P Burglar Event 26 P Access Event 26 P User Event 26 P Test Event 26 P Diag Event 26 P Auto Functions Event 26 P RPS Event 26 P Relay Event 26 P Point Event 26 P Usr Chng Evt 26 RPS Parameters 26 Panel Initiated Unattended RPS 27 RPS Passcode 27 Log Full 27 RPS Call Back 28...

Страница 130: ...y Lock 50 CC Abort Display 50 CC Cancel Display 50 Area Text 50 Area Is On 51 Area Not Ready 51 Area Is Off 51 Area Account Is On 51 Custom Function 51 Custom Function 52 CF Text 52 CF Key Strokes 52 User Interface 54 Command Authorization 54 Master Arm Delay 55 Master Arm Instant 55 Perimeter Instant 55 Perimeter Delay 55 Watch Mode 56 Perimeter Partial 56 View Area Stat 56 View Memory 56 View Po...

Страница 131: ...e to Area 66 L Display Rev 66 L Service Walk 66 L Default Text 67 L Change Skeds 67 L Invisible Walk Test 67 L C Function 128 through 131 67 L Force Arm 67 L Area O C 67 L Restricted O C 68 L Perimeter O C 68 L Send Duress 68 L Passcode Arm 68 L Passcode Disarm 68 L Security Level 68 L Disarm Level 68 L Function Level 68 Function List 69 Menu Item 69 M Function 69 M CC Address 1 through 8 69 Relay...

Страница 132: ...ross Point 89 P Fire Point 90 P Alarm Verify 90 P Resettable 90 P Alarm Abort 90 Point Assignments 91 Point Number 91 P Point Index 91 P Area Assign 92 P Debounce 92 P Relay 93 P Point Text 93 COMMAND 7 and COMMAND 9 93 CMD7 Point Index 93 CMD7 Relay 93 CMD7 Point Text 93 CMD9 Point Index 94 CMD9 Relay 94 CMD9 Point Text 94 94 Windows 94 Opening and Closing 94 Window 95 W Sunday 95 W Monday 95 W T...

Страница 133: ... Change Delete 110 Date 110 Holiday Index 110 View Holidays 110 Index 1 Days 110 Index 2 Days 110 Index 3 Days 110 Index 4 Days 110 AUX 111 SDI Automation 111 Supervise SDI 80 112 Status Rate 112 SDI RPS Parameters 113 Configuration for RPS over Network 113 RPS IP Address 115 RPS Port Number 116 Enhanced Comm 117 Path IP Address 117 Path Port Number 117 Path Poll Rate 118 Path Ack Wait 120 122 SDI...

Страница 134: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2011 ...

Отзывы: