D7212GV3 |
Program Entry Guide | 2.0
Panel and Area Wide Parameters
EN
| 48
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
CC# Enter Key Relay
Default:
0
Selection:
1 to 24, A, B, C
0
The [ENTER] key is not used to
activate a relay.
1 to 24, A,
B, C
Assign the relay number that
activates when [ENTER] is pressed
at this keypad after the user enters a
valid passcode.
Enter Key Relay:
Program the relay number that
activates momentarily for 10 sec when a user enters
a valid passcode and presses the [ENTER] key on
the keypad. Two events are generated when this
function is used: RELAY ### SET with User ID, and
RELAY ### RESET without User ID. The system
logs this action as two events.
Entering a valid code and pressing [ENTER] at a
keypad silences a ringing bell.
This feature is not restricted by the scope of the
keypad, so any user can perform this operation at the
configured keypad.
When programmed to activate a relay,
the [ENTER] key cannot be used for any
other function.
Relays used for this function must not be
shared with any other point, sensor reset,
control panel, or bell functions. Sharing
can cause errors in relay operation.
CC# Entr Cycl Dr
Default:
No
Selection:
Yes or No
This feature is not available with the D7212GV3.
Keep the default setting.
CC# Assign Door
Default:
Blank
Selection:
1 to 8, Blank
This feature is not available with the D7212GV3.
Keep the default setting.
CC# Trouble Tone
Default:
Yes
Selection:
Yes or No
Yes
Panel-wide trouble tones sound and
visual displays show at this keypad.
No
Panel-wide troubles do not sound.
Visual displays still show.
This prompt determines whether this keypad, or any
keypad with the same address setting, emits the
panel-wide trouble tones (power, phone, SDI bus,
and Zonex bus).
Panel-wide trouble tones do not include
Point Troubles or Buzz on Fault.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
CC# Entry Tone
Default:
Yes
Selection:
Yes or No
Yes
This keypad sounds entry tones.
No
This keypad does not sound entry
tones.
This prompt determines whether this keypad, or any
keypad with the same address setting, emits the
entry delay tone. Any Delay point within the area
scope of this keypad starts the entry sequence.
This prompt allows you to manage the
tone by keypad. Entry Tone can also be
turned off when programming your
P##
Entry Tone Off
in
Point Index
.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
For SIA CP-01 Compliance
CC# Entry Tone
can be set to
Yes
or
No
.