4-18
Climate Class 6100i / 6000i / 8100i / 8000i
Problem
symptom
Outdoor
unit
indica-
tion
(LED1)
Malfunction
No.*
Content of diagnosis
Check point
Action
Main
Sub
Main
Sub
Indoor and
outdoor
units do
not
operate.
11-time
11
1
Outdoor unit
DC fan
Outdoor unit DC
fan driver IC error
1) Check if the fan IPM ter-
minal resistance values
are uniform.
1) Replace the outdoor
unit control PWB as-
sembly.
2) Outdoor unit fan motor
continuity check.
2) Replace the outdoor
unit fan.
2
Outdoor unit DC
fan
lock error
1) Check if the fan IPM ter-
minal resistance values
are uniform.
1) Replace the outdoor
unit control PWB as-
sembly.
2) (1): Normal
2) Replace the outdoor
unit fan.
3
Outdoor unit
DC fan
Detection error of
DC fan negative
rotation before
compressor is
driven
1) (Temporary stop for DC
fan circuit protection)
-
4
Detection error of
inverter current
for DC fan
-
1) Replace the outdoor
unit control PWB as-
sembly.
5
Outdoor unit DC
fan open connec-
tor error
1) Check connector CN3 of
the outdoor unit DC fan
motor for secure installa-
tion.
1) Correct the installation.
2) No abnormality found in
above inspection (1).
2) Replace the outdoor
unit control PWB as-
sembly.
Содержание CLC6001i 25 E
Страница 7: ...1 6 Climate Class 6100i 6000i 8100i 8000i For CLC8101i 65 HE CLC8001i 25 E CLC8001i 35 E models ...
Страница 69: ...2 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Страница 77: ...10 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Страница 87: ...20 Climate Class 6100i 6000i 8100i 8000i 7 28 Reverse Value Ass y ...
Страница 88: ...21 Climate Class 6100i 6000i 8100i 8000i Expansion Value Ass y ...