15
Climate Class 6100i / 6000i / 8100i / 8000i
Connect air conditioner to power supply
with proper voltage.
(From previous page)
13-2 error
Check ODU PWB as below method
Check if the compressor is locked.
Check if the power supply voltage is 10% lower
than rated voltage.
【Check points】
①Whether there is soldering failure on IPM shunt
resistor. (e.g. R230/231/232/233/234)
②Whether the IPM is short circuit.
(Refer to IPM check method.)
·Temperature of compressor becomes too high.