The lead wire of ODU thermistor has broken due to the edge or vibration.
The attachment of connector has broken by inside tension due to unsuitable wiring process.
Check if ODU thermistors are firmly installed and
connected with ODU PWB properly.
Check if the resistance of each ODU thermistor is
correct as shown in graph below.
(First remove the connector from the PWB, and
then measure the resistance.)
Correct the installation of thermistors