Installation
www.bora.com
[4]
Silencer
[5]
Universal plinth fan
[6]
Universal control unit
X
X
Push the 90° diverter [2] onto the angled ducting piece
[3].
X
X
Position the plinth fan [5].
Q
Q
To facilitate positioning, the inlet nozzle on the plinth fan
can be removed. To do this, please see the assembly
instructions for the ULS universal plinth fan.
X
X
Connect the silencer [4] to the plinth fan [5].
X
X
Connect the silencer [4] to the 90° diverter [2].
Q
Q
There is also the option of gluing the connections
between the ducting sections and the plinth fan with
UDB sealing tape.
INFO
Position the plinth fan and the universal
control unit in such a way that they are easily
accessible and removable for maintenance
work.
Q
Q
The maximum exhaust air duct length with a fan is 6 m.
Q
Q
The minimum cross-section of the air ducts must
be 176 cm², which equates to a round pipe with
a diameter of 150 mm or the BORA Ecotube duct
system.
Q
Q
For the ducting, only use stable duct elements with
smooth pipe interiors. Do not use flexible or fabric
tubes.
6.8.4 Installing the additional fan
X
X
Install the additional fan in the exhaust duct.
X
X
Ensure that a minimum clearance of 3 m is maintained
between the fan units.
X
X
Only use BORA universal fans with your BORA cooktop
extractor system.
6.9 Operating the cooktop extractor
with a fireplace that depends on
the air in the room
INFO
The state and regional laws and regulations
must be observed with regard to the exhaust
duct design. A sufficient air supply must be
ensured.
Fireplaces that depend on the air in the room (e.g. gas,
oil, wood or coal-fired heaters, continuous-flow water
heaters, instantaneous water heaters) draw in air from
the room in which they are installed and release the
exhaust fumes into the outside air via an exhaust system
(e.g. chimney).
If the cooktop extractor is used in exhaust mode, it draws
in air from the room in which it is installed as well as from
neighbouring rooms. If there is insufficient air supply, low
pressure will occur. Toxic gases could be drawn out of the
chimney or extraction ducting and back into the room.
6.8.2 Connect the duct system to the
device.
2
2
3
1
Fig. 6.34 Connecting to the duct system.
[1]
Output nozzles
[2]
Seal
[3]
Ducting piece
X
X
Pull out the seal [2] on the connection fitting [1] of the
device. This means stretching the seal [2] slightly.
X
X
Push the duct piece [3] to be connected with the
sleeve on the connection fitting [1] with the seal [2].
X
X
Make sure the seal [2] does not move.
INFO
When fitting the seal, make sure it fits and
forms an air-tight seal with the connection duct
piece when compressed.
6.8.3 Standard setup PKA
1
2
3
4
5
6
Fig. 6.35 Standard setup PKA
[1]
Cooktop extractor
[2]
90° diverter
[3]
Bent ducting piece