ALARM LOOP CONFIGURATION PARAMETERS
Each of the two controller’s loops has the same configuration parameter,
Arming Delay
. In all the
controller operation modes, except for the Swing-beam Barrier
mode, this parameter defines the de-
lay time for starting alarm loop condition monitoring after the Loop Arming command has been re-
ceived. In Swing-beam Barrier operation mode loops 1 and 2 can not be used for security aims since
they are used in access control strategy (sensors detecting a car presence are connected to them),
so for this operation mode the value of this parameter is ignored.
The arming delay is set in seconds within 0 — 255s range. Default value (the factory setting) is 0 for
both loops.
RELAY CONFIGURATION PARAMETERS
Configuration parameters for each of the two controller’s relays are given in Table 8.
Table 8. Relay Configuration Parameters
Parameter Description
Range
Default
Value
Executive
Program
Defines a way the relay is controlled
if access is granted
3 - Switch On for a Time
4 – Switch Off for a Time
3
Relay Activation
Time
Maximal time of transmitting the re-
lay control signal (program) if access
is granted
0.125…8192s
(0.125s…
…2h 16min 32s)
5 s
Switch Off After
Door Being Opened
Causes the selected relay executive
program to be interrupted when the
door is being opened (when the pas-
sage has been detected) before the
Relay Activation Time has been ex-
pired
On/Off On
Switch Off After
Door Being Closed
Causes the selected relay executive
program to be interrupted when the
door has just been closed after user
passing
On/Off Off
The
Executive Program
parameter defines the way to control a relay automatically while granting
access. The executive program 3 (Switch On for a Time) is used to control normally open electrome-
chanical locks and strikes, turnstiles, swing-beam barrier openers, gates drives and so on. Initially the
relay contacts are opened (the relay is switched off). When the access has been granted the relay
contacts are closed (the relay is switched on) for a given time. The executive program 4 (Switch Off
for a Time) is used to control normally closed electromagnetic locks. Initially the relay contacts are
closed (the relay is switched on) and when the access has been granted the relay contacts ear
opened (the relay is switched off) for a specified time (see below).
Содержание S2000-2
Страница 1: ...Orion ISS Access Controller S2000 2 User s Manual ISO 9001 ...
Страница 5: ...S2000 2 Features and Design 5 www bolid com FEATURES AND DESIGN ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...S2000 2 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 12: ...Orion ISS www bolid com 12 ...
Страница 13: ...S2000 2 Operating 13 www bolid com OPERATING ...
Страница 47: ...S2000 2 Installation 47 www bolid com INSTALLATION ...
Страница 67: ...S2000 2 S2000 2 Programming 67 www bolid com S2000 2 PROGRAMMING ...
Страница 89: ...S2000 2 Maintenance 89 www bolid com MAINTENANCE ...
Страница 94: ...Orion ISS www bolid com 94 ...
Страница 95: ...S2000 2 95 www bolid com Appendix Connecting Some Models of Readers to the S2000 2 Controller ...
Страница 100: ...4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 513 32 35 Email info bolid ru www bolid com ...