Orion ISS
www.bolid.com
36
−
None
(the S2000-2 controller is not checking any anti-passback rule)
−
Hard
−
Timed
−
Soft
The
Hard
Anti-passback
rule requires to prohibit a second passage to a zone up to the moment of
logging the exit from it. If someone attempts to violate the rule, access is denied and the ACCESS
DENIED message is generated with the
Anti-passback rule violation
attribute.
The
Soft Anti-passback
rule does not prohibit a second passage but in case of its violation the AC-
CESS GRANTED and PASSAGE messages are generated with the
Anti-passback rule violation
at-
tribute.
The
Timed Anti-passback
rule uses an additional
Anti-passback Lockout Reriod
parameter. During
this time period since passing to an access zone the S2000-2 controller is operating as for
Hard Anti-
passback
rule (repeated access requests to the zone without exiting it are rejected and ACCESS
DENIED messages are generated). After expiration of the specified time the S2000-2 controller is
operating as for
Soft Anti-passback
rule (second access is granted, but the ACCESS GRANTED and
PASSAGE messages are generated with the
Anti-passback rule violation
attribute).
If the S2000-2 controller operates as a part of an
Orion
system, it checks anti-passback rules taking
into account all passages to the access zone registered by other controllers of the system (the
Global
anti-passback rule is implemented). So, if an access zone has several access points (for example,
several gate houses to enter/exit from the company premises or several turnstiles operating in paral-
lel) equipped with S2000 controllers, entering the zone via one of the access points will lock the ac-
cess to the zone through other access points and unlock the access from this zone. Vice versa, leav-
ing the zone via one of the access points will lock exit from the zone and unlock entry to it (of course,
if the anti-passback rule checking is programmed for the key presented).
Anti-passback rules will operate properly at an access point between two zones only if two following
requirements are met:
−
Authorized passing from one zone to another is only possible via the access points controlled
by S2000-2 controllers
−
Each the access point has to be equipped with two readers providing identification both for entry
and for exit as well as a passage sensors.
For the Global anti-passback mode to operate properly all readers controlling entry to a zone must be
programmed with the same
Access zone number
. Checking anti-passback rules each S2000-2 con-
troller takes into account a passage registered by any other S2000-2 controller of the Orion system if
the passage is relevant to the two access zones which are assigned with the S2000-2 in question.
Passages relevant to zones not assigned with the S2000-2 controller are ignored.
Содержание S2000-2
Страница 1: ...Orion ISS Access Controller S2000 2 User s Manual ISO 9001 ...
Страница 5: ...S2000 2 Features and Design 5 www bolid com FEATURES AND DESIGN ...
Страница 8: ...Orion ISS www bolid com 8 ...
Страница 9: ...S2000 2 Specifications 9 www bolid com SPECIFICATIONS ...
Страница 12: ...Orion ISS www bolid com 12 ...
Страница 13: ...S2000 2 Operating 13 www bolid com OPERATING ...
Страница 47: ...S2000 2 Installation 47 www bolid com INSTALLATION ...
Страница 67: ...S2000 2 S2000 2 Programming 67 www bolid com S2000 2 PROGRAMMING ...
Страница 89: ...S2000 2 Maintenance 89 www bolid com MAINTENANCE ...
Страница 94: ...Orion ISS www bolid com 94 ...
Страница 95: ...S2000 2 95 www bolid com Appendix Connecting Some Models of Readers to the S2000 2 Controller ...
Страница 100: ...4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 513 32 35 Email info bolid ru www bolid com ...