DATE PRINTED: 2/8/05 Revision Date: 04/15/04
OM-2205 Page 30
Frequent pilot
outage problems.
Pilot adjusted too low.
Switch wires may be
grounding out.
Thermocouple worn.
Adverse wind conditions.
⇒
Adjust pilot and clean if required.
⇒
Check switch wires.
⇒
Check thermocouple millivolts (see above).
⇒
Check termination location is not subject to adverse enviromental
conditions.
The main burner
shuts off when the
appliance is warm.
Pilot flame lifting of
thermopile.
⇒
Check thermopile voltage from start up. If millivolts drop dramatically
it is an indication that the pilot is lifting. Check the vent is correctly
attached.
Excessive soot on
burner or logs.
Incorrect aeration
adjustment.
Incorrect venting.
⇒
Check aeration setting.
⇒
Check that venting is correctly attached.
Sharp blue flames
lifting off burner.
Incorrect aeration
adjustment.
⇒
Reduce primary aeration adjustment.
Convection blower
does not operate.
No power supply.
Thermal snap switch
lose or defective.
Lose electrical
connection.
Defective speed
controller.
Defective blower.
⇒
Check electrical supply to unit.
⇒
Check for correct positioning of the snap switch. You can short out
the snap disk to check it’s operation.
⇒
Check all electrical connections are secure.
⇒
Short out speed controller to check for defective operation.
⇒
Check terminals on speed controller. If you have 120VAC the blower
motor is defective.
APPENDIX ‘D’ (TROUBLE SHOOTING)
SERVICE HISTORY
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
DATE
CORRECTIVE ACTION (INCLUDE REPLACEMENT PARTS)