CB-100-1
38
3
Technical data
• Operating voltage
– 380 .. 480 V/3/50 Hz.
– 380 .. 480 V/3/60 Hz.
– Voltage tolerance ±10%.
– Operation on IT networks on request.
To obtain compatibility with this network configur-
ation and the network monitoring installed there,
the integrated EMC filters must be deactivated
and special external filters must be used.
– Operation on generators, emergency power unit
and networks equipped with power factor correc-
tion units only after consultation with BITZER.
• Earth fault current: > 10 mA
• Over-voltage category III
• Enclosure class - IP20 or Open Type UL and cUL
• Operating altitude and climatic conditions:
– 1000 m above sea level, capacity reduction by 1%
per 100 m up to max. 2000 m
– Class 3k3 to EN 60721-3-3
• Humidity and atmosphere:
– Non-condensing.
– Max. relative humidity 85% at 40°C.
– Non-flammable, non-corrosive and dust-free.
• Vibrations:
– Test according to EN 60068-2-6 (Fc).
10 Hz < f < 57 Hz sinusoidal 0.075 mm amplitude.
57 Hz < f < 150 Hz sinusoidal 1 g.
10 cycles per axis on each of three mutually per-
pendicular axes.