13. Defrosting at refrigerating operation
BINDER climatic chambers are very diffusion-proof. To ensure high temperature precision there is no
automatic cyclic defrosting device. The DCT™ refrigerating system largely avoids icing of the evaporation
plates. However, at very low temperatures the moisture in the air can condense on the evaporator plates
leading to icing.
Always close the door properly.
Operation with temperature set-points > +5 °C /
41 °F
at an ambient temperature of 25 °C /
77 °F
:
The air defrosts the ice cover automatically. Defrosting is continually performed.
Operation with temperature set-points < +5 °C /
41 °F
:
Icing on the evaporator is possible. Defrost the unit manually.
With temperature set-points < +5 °C /
41 °F
, regularly defrost the unit manually:
•
Set the humidity to 0 % r.H. and turn on the humidifying system at humidity switch (4).
•
Set the temperature to 40 °C /
104 °F
(Manual Mode).
•
Let the unit operate for about 30 minutes with the door closed.
Too much ice on the evaporator is noticeable by reduced refrigerating performance.
When turning off the unit following prolonged refrigerating operation below +5 °C /
41 °F
, there is danger
of overflowing due to uncontrolled defrosting of icing on the evaporator.
CAUTION
Uncontrolled defrosting of icing on the evaporator.
Danger of overflowing.
After several days of refrigerating operation below +5 °C /
41 °F
:
∅
Do NOT directly turn off the unit.
Manually defrost the unit (see description above).
Then, shut down the unit at the main power switch (3) and close the tap of the water
supply.
Содержание KBF 115 (E5.2)
Страница 5: ...KBF KBF P E5 2 02 2012 page 5 103 Product registration ...
Страница 98: ...KBF KBF P E5 2 02 2012 page 98 103 19 7 Dimensions KBF 115 ...
Страница 99: ...KBF KBF P E5 2 02 2012 page 99 103 19 8 Dimensions KBF 240 KBF P 240 ...
Страница 100: ...KBF KBF P E5 2 02 2012 page 100 103 19 9 Dimensions KBF 720 KBF P 720 ...