User Manual
Model PCS
Pneumatic Motion Control System
Option N
dividual wires from the Command Cable to PCS Terminal Block TB4 on the PC Board per above. Provide the
proper strain relief.
Option Q
ick connect command cable (2 meter Model PCS-CBL-CMD or 5 meter Model PCS-CBL-CMD-X) connector
end of the cable to the enclosure box command signal connector (this is the 6 pin connector, the connector
is keyed and can only be plugged into the correct connector). Connect the other end of the cable using the
following color codes:
Input
-Brown,
Current Position
-Black, @
Pos
-White,
Ground
-Blue. The other wires are
not used. See definitions above in the Standard Enclosure section.
7. Perform the following step for OPTION N Only.
CONNECT VALVE CABLES TO PCS PC BOARD.
Connect per the following
>
Connect all 4 Black wires from the valves to TB3 BLACK +24 VDC.
>
Connect the 2 white wires from Valves V1 and V3 to TB3 RED DIR. (Decreasing Direction)
>
Connect the 2 white wires from Valves V2 and V4 to TB3 GRN DIR. (Increasing Direction)
The following diagram below shows the location of the valves, when looking down at them.
8. CHECK ALL ELECTRICAL AND PNEUMATIC CONNECTIONS
Make sure all pneumatic connections to the actuator and PCS are correct and leak free. Double check
all electrical connections at the actuator, the PCS, the power supply and the Main Control. If all electrical
connections are correct, carefully tighten the captive plastic nut on the strain relief fittings. Do not install the
control enclosure cover yet.
9. APPLY 24 VDC POWER
With the actuator mounted in final position and the PCS or snap track mounted in its final position, apply the 24
VDC power to the PCS. The cylinder should not move since it does not yet have any pneumatic pressure.
You
may hear clicking noises and/or have a Green or Red LED on, which is normal.
TB3