Problem:
The actuator feedback has excess signal noise.
Solution:
Ensure that the feedback signal is free from electrical noise. Electro-Magnetic Interference (EMI) can
couple to the feedback signal. Employ shielded cable between the actuator and the PCS system.
Problem:
The valves are contaminated.
Solution:
The valves need rebuilt or replaced. Teflon tape or line contamination can cause valve leaks if allowed
to enter the valve. Use a liquid thread sealant and a filtration system that is rated for 5 microns.
Problem:
Possibly Nothing.
Solution:
The actuators and valves are built to minimize leakage, but not to totally eliminate it. If a stable
positioned actuator drifts toward the edge of the system deadband, the PCS will pulse to maintain position. If
the deadband is set very narrow, this correction will be more frequent.
FREQUENTLY ASKED QUESTIONS
Question:
Are there Default Settings for the Deadband, Zero, Span, and Decel settings?
Answer:
While there are no perfect default settings, the following are used as the default factory settings.
>
Deadband 0.020 VDC (20mV). Check between TP1 and TP2 with SW1 switched in the Set position.
>
Decel 1.5 VDC. Check between TP1 and TP3.
>
Zero is set to its minimum value (fully CW).
>
Span is set to its minimum value (fully CW).