7.12 Selecting the reignition fre-
quency
When the boiler functions in normal on/off
heating mode, the minimum time between two
ignitions is set at three minutes (re-ignition fre-
quency).
This time can be changed by a minimum of
zero to a maximum of eight and a half minutes
by acting on programming both from the panel
controls and the remote control.
• Enter the "programming mode" by pressing
keys 12 - 15 - 16 (Fig. 7.32) for 10 seconds
at the same time until the letters
P01
on the
LCD display, indicating that "parameter 01"
(Fig. 7.33) has been activated.
Fig. 7.32
9
10
11
12 13
14
15
16
17
Fig. 7.33
• Scroll the various parameters using keys 15
or 16 until the letters
P10
are displayed on
the LCD display, indicating that "parameter
10" (Fig. 7.34) has been activated.
Fig. 7.34
• It is possible to modify parameter 10 by
00=
0s to
100=
510s using keys 9 or 10 (each
increase or reduction by a unit on the dis-
play corresponds to 5 seconds). Ex. 36=180
seconds.
• The writing
P10
-
SEt
alternates on the dis-
play (Fig. 7.35).
Fig. 7.35
• By pressing key 12 (Fig. 7.32) confirmation
of the inserted value is obtained.
• Press keys 15 or 16 (Fig. 7.32) to exit with-
out changing the value.
• Exiting the “programming mode” is auto-
matic, after 15 minutes, or by cutting power.
Programming using the REMOTE control
Act on the programming of the REMOTE con-
trol to select a minimum time between two ig-
nitions when the boiler functions in normal on/
off heating mode.
• Press button for more than 3 seconds to
enter in
mode (Fig. 7.36).