- 61 -
INST
ALLA
TION
COMMISSIONING
Fig. 7.19
• Using keys 15 or 16 it is possible to change
the value of parameter 15 from a minimum
of
01
to a maximum of
60
based on the se-
lected bend of the K coefficient in Fig. 7.16
(the value read on the display corresponds
to K coefficients decimal values).
The writing
P15
-
SEt
alternates on the dis-
play (Fig. 7.20).
Fig. 7.20
• By pressing key 12 (Fig. 7.17) confirmation
of the inserted value is obtained.
• Press keys 15 or 16 (Fig. 7.17) to exit with-
out changing the value Fig. 7.19)
• Exiting the “programming mode” is auto-
matic, after 15 minutes, or by cutting power.
At this point the plant flow temperature will fol-
low the trend in relation to the K coefficient set.
However, if the ambient temperature is not
comfortable, the flow temperature of the heat-
ing plant can be increased or reduced by ±
15°C by acting on keys 15 (reduce) and 16
(increase) (Fig. 7.17).
Fig. 7.21
C.h. flow
temperature °C
20
20 15 10
5
0
-5 -10 -15 -20 -25
30
40
50
60
70
80
-15 °C
+ 15 °C
External temperature °C
K = 1,5
The temperature trend when changing the
setting made with keys 15 and 16 for a
K 1,5
is shown in Fig. 7.21.
Sequence for setting the K coefficient with
the remote control connected
Act on the programming of the REMOTE con-
trol to select the setting of the K coefficient.
• Electrically feed the boiler by activating the
bipolar switch envisioned during installation.
• Press button for more than 3 seconds to
enter in
(Fig. 7.22) mode.
Fig. 7.22
0
2
1
8
1
21
1 5
6
3
9
Press button
to display the
K REG
win-
dow (Fig. 7.23).