- 54 -
INST
ALLA
TION
INSTALLATION
The route of the remote control cable must
follow the route indicated in Fig. 6.17.
Allow the cables to exit the boiler by using
the relevant cable clamps R (Fig. 6.18).
6.16 Example of hydraulic plants
with hydraulic separator
(optional)
The hydraulic separator creates a reduced
load loss zone that renders the primary cir-
cuit and secondary circuit hydraulically in-
dependent.
In this case the flow rate that passes through
the circuits depends exclusively on the fea-
tures of the pumps flow rate.
Therefore, by means of a hydraulic separa-
tor, the secondary circuit's flow rate is put
into circulation only when the relative pump
is on.
When the pump of the secondary is off,
there is no circulation in the correspond-
ing circuit and therefore, the entire flow rate
pushed by the primary is by-passed through
the separator.
Thus, with the hydraulic separator, it is pos-
sible to have a constant flow rate production
circuit and a variable flow rate distribution
circuit.
Hydraulic plant examples
Top zone + low temperature zone.
Fig. 6.31
S
Low temperature
Hight temperature
External probe
Top zone + 2 low temperature zones.
Fig. 6.32
S
Low
temperature 1
Low
temperature 2
Hight
temperature
External
probe