INSTALLATION MANUAL

AUX output configuration

Aux logic= 1 - SCA gATE OPEN LIgHToutput.  

Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIgHT command output.  

Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIgHT command output.   

Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIgHT output.   

Contact stays closed for 1 second at start of operation. 
Aux logic= 5 - gATE OPEN ALARM output.  

Contact stays closed if the leaf stays open for double the set TCA time.
Aux logic= 6 - FLASHINg LIgHT output.  

Contact stays closed while leaves are operating.
Aux logic= 7 - SOLENOID LATCH output.  

Contact stays closed for 2 seconds each time gate is opened. 
Aux logic= 8 - MAgNETIC LOCK output.  

Contact stays closed while gate is closed.

Aux logic= 9 - MAINTENANCE output.

Contact stays closed once the value set for the Maintenance parameter is reached, to report that maintenance is required.  

Aux logic= 10 - FLASHINg LIgHT AND MAINTENANCE output.

Contact stays closed while leaves are operating. If the value set for the Maintenance parameter is reached, once the gate has finished moving and the leaf is closed, the contact closes 

for 10 sec. and opens for 5 sec. 4 times to report that maintenance is required.

Command input configuration

IC logic= 0 - Input configured as Start E. Operation according to 

STEP-BY-STEP MOV

. logic.  

IC logic= 1 - Input configured as Start I. Operation according to 

STEP-BY-STEP MOV

. logic.  

IC logic= 2 - Input configured as Open.  

The command causes the leaves to open. If the input stays closed, the leaves stay open until the contact is opened. When the contact is open, the automated device closes following 

the TCA time, where activated.

IC logic= 3 - Input configured as Closed.  

The command causes the leaves to close.

IC logic= 4 - Input configured as Ped. 

The command causes the leaf to open to the pedestrian (partial) opening position. Operation according to 

STEP-BY-STEP

. logic

IC logic= 5 - Input configured as Timer. 

Operation same as open except closing is guaranteed even after a mains power outage.

IC logic= 6 - Input configured as Timer Ped. 

The command causes the leaf to open to the pedestrian (partial) opening position. If the input stays closed, the leaf stays open until the contact is opened. If the input stays closed and a Start E, 

Start I or Open command is activated, a complete opening-closing cycle is performed before returning to the pedestrian opening position. Closing is guaranteed even after a mains power outage.

Safety input configuration

SAFE logic= 0 - Input configured as Phot (photocell). (fig.F, ref.1).  

Enables connection of devices not equipped with supplementary test contacts. When beam is broken, photocells are active during both opening and closing. When beam is broken 

during closing, movement is reversed only once the photocell is cleared. If not used, leave jumper inserted.
SAFE logic= 1 - Input configured as Phot test (tested photocell). (fig.F, ref.2).  

Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is 

reversed only once the photocell is cleared.
SAFE logic= 2 - Input configured as Phot op (photocell active during opening only). (fig.F, ref.1).  

Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops 

motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE logic= 3 - Input configured as Phot op test (tested photocell active during opening only (fig.F, ref.2). 

Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photo-

cell beam stays broken.
SAFE logic= 4 - Input configured as Phot cl (photocell active during closing only). (fig.F, ref.1).  

Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, move-

ment is reversed immediately. If not used, leave jumper inserted.
SAFE logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.F, ref.2). 

Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
SAFE logic= 6 - Input configured as Bar (safety edge). (fig.F, ref.3).  

Enables connection of devices not equipped with supplementary test contacts. The command reverses movement for 2 sec.. If not used, leave jumper inserted.
SAFE logic= 7 - Input configured as Bar (tested safety edge (fig.F, ref.4). 

Switches safety edge testing on at start of operation. The command reverses movement for 2 sec.
SAFE logic= 8 - Input configured as Bar 8k2 (fig.F, ref.5). Input for resistive edge 8K2.  

The command reverses movement for 2 sec..

6) SAFETY DEVICES

Note: only use receiving safety devices with free changeover contact.
6.1) TESTED DEVICES Fig. F

6.2) CONNECTION OF 1 PAIR OF NON-TESTED PHOTOCELLS FIG. C
7) CALLING UP MENUS: FIG. 1
7.1) PARAMETERS MENU (

PARA

) (PARAMETERS TABLE “A”)

7.2) LOGIC MENU (

LOGIC

)

 

(LOGIC TABLE “B”) 

7.3) DEFAULT MENU (

default

)

Restores the controller’s DEFAULT factory settings. 

7.4) LANGUAGE MENU (

language

)

Used to set the programmer’s language on the display. 

7.5) LIMIT SWITCH ADJUSTMENT MENU (

L.SW ADj

) (Fig . D)

Limit switch adjustment procedure:

1)  go to L.SW ADJ and confirm with OK.

2)  The display reads CLOSE. Use the UP and DOWN keys to move the door to the closing limit switch 

position. Confirm with OK. The display reads PRg.

3)  If prompted by the display, turn the adjustment ring: anticlockwise if the display reads UP; clock-

wise if the display reads DOWN. Once you have reached the correct position, the display reads 

OK. Confirm with the OK key. The display reads PRg.

4)  The display reads OPEN. Use the UP and DOWN keys to move the door to the opening limit switch 

position. Confirm with OK. The display reads PRg.

If the display reads KO, it means adjustment was not successful.

This may be caused by:

- the ESC key being pressed before adjustment was completed

- stored travel being too short

7.6) STATISTICS MENU

Used to view the version of the board, the total number of operations (in hundreds), the 

number of transmitters memorized and the last 30 errors (the first 2 digits indicate the 

position, the last 2 give the error code).  Error 01 is the most recent.

7.7) PASSWORD MENU

Used to set a password for the board’s wireless programming via the U-link network.

With “PROTECTION LEVEL” logic set to 1,2,3,4, the password is required to access the 

programming menus. After 10 consecutive failed attempts to log in, you will need to wait 3 

minutes before trying again. During this time, whenever an attempt is made to log in, the 

display will read “BLOC”. The default password is 1234.

8) OPEN IN OTHER DIRECTION
9) CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD PROGRAMMER 

VERSION> V1.40 (Fig. B) 

Refer to specific manual.

10) RADIO-RECEIVER (Fig. B)

The board comes ready for connection of removable radio-receiver.

The receiver’s channel 1 controls input IC1.

The receiver’s channel 2 controls terminals 26-27.

11) U-LINK OPTIONAL MODULES

Refer to the U-link instructions for the modules. 

The use of some models causes lowered radio capacity. Adjust the system using an appropriate 

antenna tuned to 433MHxz.

12) RESTORING FACTORY SETTINGS (Fig.G)

WARNING: 

this operation will restore the control unit’s factory settings and all transmitters 

stored in its memory will be deleted.

WARNINg! Incorrect settings can result in damage to property and injury to people and animals. 

- Cut off power to the board (Fig.g ref.1)

- Open the Stop input and press the - and OK keys together (Fig.g ref.2)

- Switch on the board’s power (Fig.g ref.3)

- The display will read RST; confirm within 3 sec. by pressing the OK key (Fig.g ref.4)

- Wait for the procedure to finish (Fig.g ref.5)

- Procedure finished (Fig.g ref.6)

WARNING!  Incorrect settings can result in damage to property and injury to people and animals.  

WARNING: Check that the force of impact measured at the points provided for 

by standard EN 12445 is lower than the value laid down by standard EN 12453.

For best results, it is advisable to run the autoset function with the motors idle (i.e. not over-

heated by a considerable number of consecutive operations).

16  -

  LEO B CBB 3 230 L01

D811828 00100_02

Содержание LEO B CBB 3 230 L01

Страница 1: ...terno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente las Advertencias en el interior Let op Lees de Waarschuwingen tigre aan de binnenkant zorgvuldig QUADRO COMANDO CONTROL PANEL CENTRALE DE COMMANDE SELBSTÜBERWACHENDE STEUERUNG CUADRO ...

Страница 2: ...uss von einem Paar nicht überprüften Fotozellen Conexión de 1 par fotocélulas no comprobadas Aansluiting van 1 paar fotocellen anders dan trusted device 2 1 TX1 2 1 RX1 4 5 3 SAFE 1 0 194 100 236 10 L N 11 1213 20 21 26 60 616263 646570 7172737475767778 27 404142 43 50 51 52 Y F1 100 mAT F2 6 3 AF Y ANT SHIELD Antenna Antenne Antena Antenne GND GND Connettore programmatore palmare Palmtop programm...

Страница 3: ...ally 3 complete opening closing cycles after being adjusted Après leur réglage 3 manœuvres complètes suffisent pour que les fins de course s adaptent automatiquement Die Endschalter passen sich nach drei vollständigen Manövern nach ihrer Einstellung automatisch an Los finales de carrera se adaptarán automáticamente tras 3 maniobras completas de su regulación De eindaanslagen passen zich automatisc...

Страница 4: ... 6 SAFE2 0 2 4 SAFE2 6 SAFE1 1 3 5 SAFE2 1 3 5 SAFE2 7 SAFE2 8 1 PHOT 1 PHOT OP 1 PHOT CL 1 PHOT 1 PHOT OP 1 PHOT CL 2 PHOT 2 PHOT OP 2 PHOT CL BAR 8K2 1 BAR 1 BAR 2 BAR 50 52 50 52 50 51 50 51 50 51 50 51 50 70 74 70 74 75 70 70 74 75 51 51 50 51 50 51 50 52 52 52 74 70 74 70 75 74 70 51 50 70 75 72 50 70 71 73 74 75 24V 24V 24 VSafe COM SAFE 1 SAFE 2 STOP FAULT 1 FAULT 2 NC NC NC 70 71 73 74 75 ...

Страница 5: ...H FRANÇAIS ESPAÑOL NEDERLANDS DEUTSCH ITALIANO G ON ON OFF OFF S1 S2 S3 OK ON ON OFF OFF S1 S2 S3 OK 70 71 COM STOP S1 S2 S3 OK S1 S2 S3 OK 8888 rst8 8888 1 2 3 4 6 5 3s LEO B CBB 3 230 L01 5 D811828 00100_02 ...

Страница 6: ... posizione dello sblocco ER01 Test fotocellule fallito Verificare collegamento fotocellule e o impostazioni logiche ER02 Test costa fallito Verificare collegamento coste e o impo stazioni logiche ER03 Test fotocellule apertura fallito Verificare collegamento fotocellule e o impostazione parametri logiche ER04 Test fotocellule chiusura fallito Verificare collegamento fotocellule e o impostazione pa...

Страница 7: ...unaetichettarelativaalfunzionamentodellosblocco manuale dell automazione e apporla vicino all organo di manovra Assicurarsi che durante la manovra siano evitati o protetti i rischi meccanici ed inparticolarel impatto loschiacciamento ilconvogliamento ilcesoiamentotra parte guidata e parti circostanti Dopo aver eseguito l installazione assicurarsi che il settaggio dell automazione motore sia corret...

Страница 8: ...sori 50 24V Uscita alimentazione accessori 51 24V 52 24 Vsafe Uscita alimentazione per dispositivi di sicurezza verificati trasmettitore fotocellule e trasmettitore costa sensibile Uscita attiva solo durante il ciclo di manovra Comandi 60 Comune Comune ingressi IC 1 e IC 2 61 IC 1 Ingresso di comando configurabile 1 N O Default START E START E START I OPEN CLOSE PED TIMER TIMER PED Far riferimento...

Страница 9: ...so il funzionamento della fotocellula in apertura In fase di chiusura inverte immediatamente Se non si utilizza lasciare il ponticello inserito Logica SAFE 5 Ingresso configurato come Phot cl test fotocellula verificata attiva solo in chiusura Fig F rif 2 Attiva la verifica delle fotocellule ad inizio manovra In caso di oscuramento è escluso il funzionamento della fotocellula in apertura In fase d...

Страница 10: ... di impatto verificare che con il valore impostato vengano rispettate le norme di sicurezza vigenti Installare se necessario dispositivi di sicurezza antischiacciamento Sp Disab ostacolo 0 200 0 Spazio disabilitazione inversione Disabilita il rilevamento ostacolo costa attiva in prossimità del finecorsa in chiusura 0 nessuna disabilitazione 200 disabilitazione massima ATTENZIONE Influisce direttam...

Страница 11: ...a 0 0 L impulso degli ingressi configurati come Start E Start I Ped hanno effetto durante l apertura 1 L impulso degli ingressi configurati come Start E Start I Ped non hanno effetto durante l apertura INV DIREZ AP Inversione direzione di apertura 0 0 Funzionamento standard Vedi FIG D1 1 Viene invertito il verso di apertura rispetto al funzionamento standard Vedi FIG D1 SAFE 1 Configurazione dell ...

Страница 12: ...LT1 12 Ingresso configurato come sicurezza Phot op test fotocellula verificata attiva solo in apertura L ingresso 3 EXPI2 della scheda di espansione ingressi uscite viene commutato automaticamente in ingresso verifica dispositivi di sicurezza EXPFAULT1 13 Ingresso configurato come sicurezza Phot cl test fotocellula verificata attiva solo in chiusura L ingresso 3 EXPI2 della scheda di espansione in...

Страница 13: ...ivated SWO SWO motor opening limit switch input activated rls Mechanical release activated Check position of release ER01 Photocell test failed Check photocell connection and or logic settings ER02 Safety edge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Check photocell connection and or param eter logic setting ER04 Closing photocell test faile...

Страница 14: ...n a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant protective measures taken and more specifically that nothing can be banged crushed caughtorcutbetweenthepartbeingoperate...

Страница 15: ... ENCODER power supply 41 REF SWE 42 A RS485 ENCODER communication 43 B RS485 Accessories power supply 50 24V Accessories power supply output 51 24V 52 24 Vsafe Tested safety device power supply output photocell transmitter and safety edge transmitter Output active only during operating cycle Commands 60 Common IC 1 and IC 2 inputs common 61 IC 1 Configurable command input 1 N O Default START E STA...

Страница 16: ...ed during opening During closing move ment is reversed immediately If not used leave jumper inserted SAFE logic 5 Input configured as Phot cl test tested photocell active during closing only fig F ref 2 Switches photocell testing on at start of operation In the event beam is broken photocell operation is disabled during opening During closing movement is reversed immediately SAFE logic 6 Input con...

Страница 17: ...BY STEP MOVEMNT Step by step movement 0 0 Inputs configured as Start E Start I Ped operate with 4 step logic step by step mov 2 STEP 3 STEP 4 STEP CLOSED OPENS OPENS OPENS DURING CLOSING STOPS OPEN CLOSES CLOSES CLOSES DURING OPENING STOP TCA STOP TCA AFTER STOP OPENS OPENS OPENS 1 Inputs configured as Start E Start I Ped operate with 3 step logic Pulse during closing reverses movement 2 Inputs co...

Страница 18: ...r the password to access the programming menus The default password is 1234 E The option of editing the board s parameters via the U link network is disabled SERIAL MODE Serial mode Identifies how board is configured in a BFT network connection 0 0 Standard SLAVE board receives and communicates commands diagnostics etc 1 Standard MASTER board sends activation commands START OPEN CLOSE PED STOP to ...

Страница 19: ...ctive during opening only 9 Input configured as Phot cl safety photocell active during closing only 10 Input configured as Bar safety safety edge EXPO1 Configuration of EXPO2 output on input output expansion board 4 5 1 1 Output configured as SCA gate open light 2 Output configured as Courtesy Light command 3 Output configured as Zone Light command 4 Output configured as Stair Light EXPO2 Configur...

Страница 20: ...ouillage mécanique Vérifiez la position du déverrouillage ER01 Essai photocellules échoué Vérifier connexion photocellules et ou configurations logiques ER02 Essai linteau échoué Vérifier connexion linteaux et ou configurations logiques ER03 Essai photocellules ouverture échoué vérifier connexion photocellules et ou configuration paramètres logiques ER04 Essai photocellules fermeture échoué vérifi...

Страница 21: ...tretien ou les réparations Le Fabricant décline toute responsabilité quant à la sécurité et au bon fonctionnement de l automatisation en cas d utilisation de composants d autres Fabricants Ne modifier d aucune façon les composants de l automatisation sans l autorisa tion expresse du Fabricant Informer l utilisateur de l installation sur les risques résiduels éventuels sur les systèmes de commande ...

Страница 22: ...DEUR 43 B RS485 Alimentation des accessoires 50 24V Sortie alimentation accessoires 51 24V 52 24 Vsafe Sortie alimentation des dispositifs de sécurité vérifiés émetteur photocellules et émetteur linteau sensible Sortie active uniquement pendant le cycle de manœuvre Commandes 60 Commun Commun entrées IC 1 et IC 2 61 IC 1 Entrée de commande configurable 1 N O Défaut START E START E START I OPEN CLOS...

Страница 23: ...st exclu En phase de fermeture inverse immédiatement Si vous ne l utilisez pas laissez la barrette en place Logique SAFE 5 Entrée configurée comme Phot cl test photocellule vérifiée active uniquement à la fermeture Fig F réf 2 Active la vérification des photocellules au début de la manoeuvre En cas d obscurcissement le fonctionnement de la photocellule en ouverture est exclu En phase de fermeture ...

Страница 24: ... Logique Définition Défaut Cochez le réglage accompli Options TCA Temps fermeture automatique 0 0 Logique non active 1 Active la fermeture automatique MOUVT PAS A PAS Mouvement pas à pas 0 0 Les entrées configurées comme Start E Start I Ped fonctionnement avec la logique 4 pas Mouvement pas à pas 2 PAS 3 PAS 4 PAS fermée ouvre ouvre ouvre En fermeture STOP ouverte ferme ferme ferme En ouverture ST...

Страница 25: ...hotocellule vérifiée active uniquement à l ouverture 4 Entrée configurée comme Phot cl photocellule active uniquement à la fermeture 5 Entrée configurée comme Phot cl test photocellule vérifiée active uniquement à la fermeture 6 Entrée configurée comme Bar linteau sensible 7 Entrée configurée comme Bar linteau sensible vérifiée IC 1 Configuration de l entrée de commande IC 1 61 0 0 Entrée configur...

Страница 26: ...nt en entrée vérification dispositifs de sécurité EXPFAULT1 14 Entrée configurée comme sécurité Bar linteau sensible vérifié L entrée 3 EXP12 de la carte d expansion des entrées sorties est commutée automatiquement en entrée vérification dispositifs de sécurité EXPFAULT1 EXPI2 Configuration de l entrée EXPI2 dans la carte d expansion des entrées sorties 1 3 0 0 Entrée configurée comme commande Sta...

Страница 27: ...otors SWO rls Aktivierung mechanische Entsperrung Die Position der Entsperrung überprüfen ER01 Test Fotozellen fehlgeschlagen Überprüfung Anschluss Fotozellen und oder Einstellungen Logiken ER02 Test Leiste fehlgeschlagen Überprüfung Anschluss Leisten und oder Einstellungen Logiken ER03 Test Fotozellen Öffnung fehlgeschlagen Überprüfung Anschluss Fotozellen und oder Einstellung Parameter Logiken E...

Страница 28: ... allen Wartungs und Reparaturarbeiten ausschließlich Originaler satzteile Die Firma haftet nicht für die Sicherheit und den ordnungsgemäßen Betrieb der Automatik falls Komponenten von anderen Herstellern verwendet werden Nehmen Sie keine Änderungen an den Komponenten der Automatik vor die von der Firma nicht ausdrücklich genehmigt werden Unterweisen Sie die Benutzer der Anlage hinsichtlich der ang...

Страница 29: ...gang Stromversorgung Zubehör 51 24V 52 24 Vsafe Ausgang Stromversorgung für überprüfte Sicherheitsvorrichtungen Sender Fotozellen und Sender Tastleiste Ausgang nur aktiv während des Manöverzyklusses Bedienelemente 60 Gemein Gemeine Eingänge IC 1 und IC 2 61 IC 1 Konfigurierbarer Steuereingang 1 N O Default START E START E START I OPEN CLOSE PED TIMER TIMER PED Bitte nehmen Sie auf die Tabelle Konf...

Страница 30: ...direkt um Falls nicht verwendet überbrückt lassen Logik SAFE 5 Als Phot cl test konfigurierter Eingang überprüfte Fotozelle aktiv nur bei Schließung Fig F Pos 2 Aktiviert die Überprüfung der Fotozellen bei Beginn des Manövers Deaktiviert beim Öffnen das Funktionieren der Fotozelle bei Abdunkelung Beim Schließen schaltet sie direkt um Logik SAFE 6 Als Bar konfigurierter Eingang Tastleiste Fig F Pos...

Страница 31: ...ptionen TCA Zeit automatische Schließung 0 0 Logik nicht aktiv 1 Aktiviert die automatische Schließung BEW SCHRITT SCHRITT Bewegung Schritt Schritt 0 0 Die als Start E Start I und Ped konfigurierten Eingänge funktionieren mit der Logik 4 Schritte Bewegung Schritt Schritt 2 Schritt 3 Schritt 4 Schritt geschlossen Öffnung Öffnung Öffnung bei SchlieSSung STOPP offen SchlieSSung SchlieSSung SchlieSSun...

Страница 32: ...e Fotozelle aktiv nur bei Öffnung 4 Als Phot cl konfigurierter Eingang Fotozelle aktiv nur bei Schließung 5 Als Phot cl test konfigurierter Eingang überprüfte Fotozelle aktiv nur bei Schließung 6 Als Bar konfigurierter Eingang Tastleiste 7 Als Bar konfigurierter Eingang überprüfte Tastleiste IC 1 Konfigurierung des Steuereingangs IC 1 61 0 0 Als Start E konfigurierter Eingang 1 Als Start I konfigu...

Страница 33: ...gang Überprüfung Sicherheitsvorrichtungen umgeschaltet EXPFAULT1 14 Als Sicherheit Bar konfigurierter Eingang überprüfte Tastleiste Der Eingang 3 EXPI2 der Erweiterungskarte Einmgänge Ausgänge wird automatisch auf Eingang Überprüfung Sicherheitsvorrichtungen umgeschaltet EXPFAULT1 EXPI2 Konfigurierung des Eingangs EXPI2 der erweiterungskarte Eingänge Ausgänge 1 3 0 0 Als Befehl Start E konfigurier...

Страница 34: ...radafinaldecarreraaperturadelmotorSWO rls Activacióndesbloqueomecánico Comprobarlaposicióndeldesbloqueo ER01 Prueba fotocélulas fallida Comprobar conexión fotocélulas y o configuraciones lógicas ER02 Prueba canto fallida Comprobarconexióncantosy oconfiguracioneslógicas ER03 Prueba fotocélulas apertura fallida comprobar conexión fotocélulas y o configuración parámetros lógicas ER04 Prueba fotocélul...

Страница 35: ...eparación La Empresa no se responsabiliza de la seguridad y el buen funcionamiento de la automatización en caso que se utilicen componentes de otros fabricantes No realizar ninguna modificación a los componentes de la automatización si no se cuenta con autorización expresa por parte de la Empresa Instruir al usuario de la instalación sobre los eventuales riesgos residuales los sistemas de mando ap...

Страница 36: ...ntación ENCODER 41 REF SWE 42 A RS485 Comunicación ENCODER 43 B RS485 Alimentación accesorios 50 24V Salida alimentación accesorios 51 24V 52 24 Vsafe Salida alimentación para dispositivos de seguridad comprados transmisor fotocélulas y transmisor canto sensible Salida activa sólo durante el ciclo de maniobra Mandos 60 Común Común entradas IC 1 y IC 2 61 IC 1 Entrada de mando configurable 1 N O De...

Страница 37: ...E El contacto queda cerrado durante 2 segundos en cada apertura Lógica Aux 8 Salida para CERRADURA ELÉCTRICA CON IMANES El contacto queda cerrado con cancela cerrada Lógica Aux 9 Salida MANTENIMIENTO El contacto permanece cerrado cuando se alcanza el valor configurado en el parámetro Mantenimiento para señalar la solicitud de mantenimiento Lógica Aux 10 Salida PARPADEANTE Y MANTENIMIENTO El contac...

Страница 38: ...ático MOV PASO A PASO Movimiento paso a paso 0 0 Las entradas configuradas como Start E Start I Ped funcionan con la lógica 4 pasos Movimiento paso a paso 2pasos 3 pasos 4 pasos cerrada abre abre abre en fase de cierre STOP abierta cierra cierra cierra enfasedE apertura STOP TCA STOP TCA después de stop abre abre abre 1 Las entradas configuradas como Start E Start I Ped funcionan con la lógica 3 p...

Страница 39: ...rada configurada como Bar canto sensible 7 Entrada configurada como Bar canto sensible comprobado IC 1 Configuración de la entrada de mando IC 1 61 0 0 Entrada configurada como Start E 1 Entrada configurada como Start I IC 2 Configuración de la entrada de mando IC 2 62 4 2 Entrada configurada como Open 3 Entrada configurada como Close IC 3 Configuración de la entrada de mando IC 3 64 2 4 Entrada c...

Страница 40: ...nte en entrada control dispositivos de seguridad EXPFAULT1 14 Entrada configurada como seguridad Bar canto sensible comprobado La entrada 3 EXPI2 de la tarjeta de expansión entradas salidas se conmuta automáticamente en entrada control dispositivos de seguridad EXPFAULT1 EXPI2 Configuración de la entrada EXPI2 en la tarjeta de expansión entradas salidas 1 3 0 0 Entrada configurada como mando Start...

Страница 41: ... openingsaanslag van motor SWO rls Activering mechanische deblokkering Positie van de deblokkering controleren ER01 Test fotocellen mislukt Aansluitingfotocellenen ofinstellinglogica scontroleren ER02 Test rand mislukt Aansluitingrandenen ofinstellinglogica scontroleren ER03 Test fotocellen opening mislukt aansluitingfotocellenen ofinstellingparameters logica s controleren ER04 Test fotocellen slu...

Страница 42: ...ken voor alle onderhouds of repara tiewerkzaamheden Het Bedrijf wijst iedere willekeurige verantwoordelijkheid af uit veiligheidsredenen en vanwege de goede werking van het automatiseringssysteem als er onderdelen van andere fabrikanten gebruikt worden Geen enkele wijziging uitvoeren aan de componenten van het automatiseringssys teem indien niet uitdrukkelijk door het Bedrijf geautoriseerd De gebr...

Страница 43: ...Voeding ENCODER 41 REF SWE 42 A RS485 Communicatie ENCODER 43 B RS485 Voeding ac cessoires 50 24V Uitgang voeding accessoires 51 24V 52 24 Vsafe Uitgang voeding voor trusted veiligheidsinrichtingen zender fotocellen en zender gevoelige rand Uitgang alleen actief tijdens de manoeuvrecyclus Commando s 60 Normaal Normaal ingangen IC 1 en IC 2 61 IC 1 Configureerbare ingang van commando 1 N O Default ...

Страница 44: ...eßen schaltet sie direkt um Falls nicht verwendet überbrückt lassen Logik SAFE 5 Als Phot cl test konfigurierter Eingang überprüfte Fotozelle aktiv nur bei Schließung Fig F Pos 2 Aktiviert die Überprüfung der Fotozellen bei Beginn des Manövers Deaktiviert beim Öffnen das Funktionieren der Fotozelle bei Abdunkelung Beim Schließen schaltet sie direkt um Logik SAFE 6 Als Bar konfigurierter Eingang Ta...

Страница 45: ...he Sluiting 0 0 Logica niet actief 1 Activeert de automatische sluiting STEP BY STEP MOVEMNT Beweging passo passo 0 0 De ingangen geconfigureerd als Start E Start I Ped werken met de 4 staps logica stap voor stap beweging 2 STAPS 3 STAPS 4 STAPS GESLOTEN OPENT OPENT OPENT BIJ SLUITING STOP OPEN SLUIT SLUIT SLUIT BIJ OPENING STOP TCA STOP TCA NA STOP OPENT OPENT OPENT 1 De ingangen geconfigureerd a...

Страница 46: ...alleen actief bij sluiting 6 Ingang geconfigureerd als Bar gevoelige rand 7 Ingang geconfigureerd als Bar trusted gevoelige rand IC 1 Configuratie van de commando ingang IC 1 61 0 0 Ingang geconfigureerd als Start E 1 Ingang geconfigureerd als Start I IC 2 Configuratie van de commando ingang IC 2 62 4 2 Ingang geconfigureerd als Open 3 Ingang geconfigureerd als Close IC 3 Configuratie van de comma...

Страница 47: ...h omgezet in ingang controle veiligheidsinrichtingen EXPFAULT1 14 Ingang geconfigureerd als beveiliging Bar gevoelige rand als trusted device De ingang 3 EXPI2 van de uitbreidingskaart ingangen uitgangen wordt automatisch omgezet in ingang controle veiligheidsinrichtingen EXPFAULT1 EXPI2 Configuratie van de ingang EXPI2 in de uitbreidingskaart ingangen uitgangen 1 3 0 0 Ingang geconfigureerd als c...

Страница 48: ...n 12 BENELUX BFT BENELUX SA 1400 Nivelles www bftbenelux be POLAND BFT POLSKA SP Z O O 05 091 ZąBKI www bft pl CROATIA BFT ADRIA D O O 51218 Drazice Rijeka www bft hr PORTUGAL BFT SA COMERCIO DE AUTOMATISMOS E MATERIAL DE SEGURANCIA 3020 305 Coimbra www bftportugal com CZECH REPUBLIC BFT CZ S R O Praha www bft it TURKEY BFT OTOMATIK KAPI SISTEMELERI SANAY VE Istanbul www bftotomasyon com tr RUSSIA...

Отзывы: