ENGLISH
INSTALLATION MANUAL
TABLE “A” - PARAMETERS MENU - (
PARA
)
Parameter
min.
max.
Default
Personal
Definition
Description
TCA
0
120
10
Automatic closing time [s]
Waiting time before automatic closing.
partial
opening
1
99
40
Partial opening [%]
Adjusts partial opening percentage compared to total opening in “Partial open” mode.
OP.FORCE
1
99
80
Leaf force during opening
[%]
Force exerted by leaf/leaves during opening.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices where
necessary.
CLS.FORCE
1
99
80
Leaf force during closing
[%]
Force exerted by leaf/leaves during closing.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices where
necessary.
Rev. Dis.
space
0
200
0
Reverse disabling space
Disables obstacle/curb detection near the limit stop in closing
0 = no disabling 200 = disabling Maximum
WARNING: It affects impact force directly: make sure that current safety require-
ments are met with the set value (*). Install anti-crush safety devices where necessary.
Maintenance
0
250
0
Programming number of
operations for maintenance
threshold
[in hundreds]
Allows you to set a number of operations after which the need for maintenance will be re-
ported on the AUX output configured as Maintenance or Flashing Light and Maintenance .
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
TABLE “B” - LOGIC MENU - (
LOGIC
)
Logic
Definition
Default
Cross out
setting
used
Optional extras
TCA
Automatic Closing
Time
0
0
Logic not enabled
1
Switches automatic closing on
STEP-BY-STEP
MOVEMNT
Step-by-step
movement
0
0
Inputs configured as Start E, Start I,
Ped operate with 4-step logic.
step-by-step mov.
2 STEP
3 STEP
4 STEP
CLOSED
OPENS
OPENS
OPENS
DURINg
CLOSINg
STOPS
OPEN
CLOSES
CLOSES
CLOSES
DURINg
OPENINg
STOP + TCA STOP + TCA
AFTER STOP
OPENS
OPENS
OPENS
1
Inputs configured as Start E, Start I,
Ped operate with 3-step logic. Pulse
during closing reverses movement.
2
Inputs configured as Start E, Start I,
Ped operate with 2-step logic. Move-
ment reverses with each pulse.
PRE-ALARM
Pre-alarm
0
0
The flashing light comes on at the same time as the motor(s) start.
1
The flashing light comes on approx. 3 seconds before the motor(s) start.
HOLD-TO-RUN
Deadman
0
0
Pulse operation.
1
Deadman mode.
Input 64 is configured as OPEN UP.
Input 65 is configured as CLOSE UP.
Operation continues as long as the OPEN UP or CLOSE UP keys are held down.
WARNING: safety devices are not enabled.
2
Emergency Deadman mode. Usually pulse operation.
If the board fails the safety device tests (photocell or safety edge, Er0x) 3 times in a row, the device is
switched to Deadman mode, which will stay active until the OPEN UP or CLOSE UP keys are released.
Input 64 is configured as OPEN UP.
Input 65 is configured as CLOSE UP.
WARNING: with the device set to Emergency Deadman mode, safety devices are not enabled.
3
Pulse operation during opening.
Deadman mode during closing.
Input 64 is configured as PULSE OPEN.
Input 65 is configured as CLOSE UP.
WARNING: safety devices are not enabled during closing.
IBL OPEN
Block pulses during
opening
0
0
Pulse from inputs configured as Start E, Start I, Ped has effect during opening.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during opening.
OPEN IN OTHER
DIRECT.
Open in other
direction
0
0
Standard operating mode (see Fig. D1).
1
Opens in other direction to standard operating mode (see Fig. D1).
LEO B CBB 3 230 L01-
17