INSTALLATION MANUAL
Logic
Definition
Default
Cross out
setting
used
Optional extras
SAFE 1
Configuration of
safety input SAFE 1.
72
0
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
SAFE 2
Configuration of
safety input SAFE 2.
74
6
4
Input configured as Phot cl (photocell active during closing only).
5
Input configured as Phot cl test (tested photocell active during closing only).
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
8
Input configured as Bar 8k2.
SAFE 3
Configuration of
safety input SAFE 3.
77
2
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
4
Input configured as Phot cl (photocell active during closing only).
5
Input configured as Phot cl test (tested photocell active during closing only).
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
IC 1
Configuration of
command input IC 1.
61
0
0
Input configured as Start E.
1
Input configured as Start I.
IC 2
Configuration of
command input IC 2.
62
4
2
Input configured as Open.
3
Input configured as Close.
IC 3
Configuration of
command input IC 3.
64
2
4
Input configured as Ped.
5
Input configured as Timer.
IC 4
Configuration of
command input IC 4.
65
3
6
Input configured as Timer Pedestrian.
Protection
level
Setting the
protection level
1
Not used
2
Not used
3
Not used
4
A - You are prompted to enter the password to access the programming menus
The default password is 1234.
E -
The option of editing the board’s parameters via the U-link network is disabled.
SERIAL MODE
Serial mode
(Identifies how board
is configured in a BFT
network connection).
0
0
Standard SLAVE: board receives and communicates commands/diagnostics/etc.
1
Standard MASTER: board sends activation commands (START, OPEN, CLOSE, PED, STOP) to other
boards.
ADDRESS
Address
0
[ ___ ]
Identifies board address from 0 to 119 in a local BFT network connection.
(see U-LINK OPTIONAL MODULES section)
EXPI1
Configuration of
EXPI1 input on
input-output expan-
sion board.
1-2
1
0
Input configured as Start E command.
1
Input configured as Start I command.
2
Input configured as Open command.
3
Input configured as Close command.
4
Input configured as Ped command.
5
Input configured as Timer command.
6
Input configured as Timer Pedestrian command.
7
Input configured as Phot (photocell) safety.
8
Input configured as Phot op safety (photocell active during opening only).
9
Input configured as Phot cl safety (photocell active during closing only).
10
Input configured as Bar safety (safety edge).
11
Input configured as Phot test safety (tested photocell).
Input 3 (EXPI2) on input/output expansion board is switched automatically to safety device test
input, EXPFAULT1.
12
Input configured as Phot op test safety (tested photocell active during opening only).
Input 3 (EXPI2) on input/output expansion board is switched automatically to safety device test
input, EXPFAULT1.
13
Input configured as Phot cl test safety (tested photocell active during closing only).
Input 3 (EXPI2) on input/output expansion board is switched automatically to
safety device test input, EXPFAULT1.
14
Input configured as Bar safety (tested safety edge).
Input 3 (EXPI2) on input/output expansion board is switched automatically to
safety device test input, EXPFAULT1.
18 -
LEO B CBB 3 230 L01
D811828 00100_02