5
HTE402559
38/47
2. Noise filter
a. The input and output power line of the controller should install noise filters
mentioned below on them.
b. Addition to them, a single phase noise filter should be installed on the input
power line prior to the clamp filter.
Clamp filter
ZCAT3035-1330 made by TDK
Single phase noise filter
RSHN2006 made by TDK-Lambda
Please wind each power lines on the clamp filters once.
You may wind the ground line together with the power lines.
Those lines must be passing through the orifice of the clamp filter twice.
Winding the ground line together with the power line results no performance-sapping.
AC200~230V、50/60Hz
Or AC100~120V、50/60Hz
Ground
Less than
Ground
Ground