![BFC VMC Series Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/bfc/vmc-series/vmc-series_instruction-manual_2746047038.webp)
5
HTE402559
37/47
CE Marking requires conditions mentioned below and installation of noise filters.
Under the conditions the controller conforms to the EC Directive.
Directives conforming to:
Low Voltage Directive (2014/35/EU) EN50178 : 1997
EMC Directive (2014/30/EU) EN61000-6-2 : 2005
EN61000-6-4 : 2007
1. Installation
a. The controller should be installed in an enclosure appropriate for IP4X.
b. The clearance between the controller and the four walls of the enclosure should
be wider than 100 mm.
c. Where more than two sets of the controller are installed in an enclosure
the controllers keep clearance of 10 mm off mutually.
d. The atmospheric temperature in the enclosure has to be kept lower than 40 degree
Celsius or a cooling fan must be provided for.
Conformity with CE Marking