5. Dial the “Setting Encoder” to set the output frequency so that “ALARM” lamp is not turned on.
The output frequency is generally adjustable manually within 3% against the auto-tuned.
6. Push “Save” button to save the data having been set.
Push
button
Storing
New data is stored
Setting Encoder
Dial
When the stroke is hunting on the constant stroke mode
reduce the gain on the Function code “G”.