5
HTE402559
31/47
The right side socket connector “E-Con1” is
used for speed change and error signal output.
The connector must be connected to one of two connectors
named “4321” on the printed circuit board.
The left side socket connector “E-Con2” is used for
control by 4 -20 mA current or two-rate-of-feed by two
external rheostats.
To use those functions an output or input cable must be connected with a special plug
connector model “XN2A-1430 by OMRON that is provided by customer.
Remove the panel and a side cover.
E-Con1
E-Con2
Location of the Connectors
Warning! : Before remove the control panel, disconnect and lock out the power supply at
the safety disconnect switch.
Caution! : Fault connection of “E-Con1” and “E-Con2” should damage VMC-controller.
There is no indication of “E-Con1” or “E-Con2” on the printed circuit board.
The connector must be connected to
one of two connectors named
“E-Con” on the printed circuit board.
Speed change/Control by 4 -20 mA current/Two-rate-of-feed control by external Rheostats
4321
4321