Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 172 / 174
Behaviour at the end of the
forced-control position
tracking the switching state
no change of switching
state
switching off
switching on
The behaviour of the output at the beginning of
a forced-control position function is directly
determined by the forced-position telegram. The
behaviour of the output at the end of the forced-
control position function can be parameterized.
At the end of the forced-control position
function, the output will be set to the switching
state last existing before forced control or to the
one tracked internally while forced control was
active. In this case, residual times of time
functions or of the staircase functions will be
tracked as well, if they have not completely
elapsed at the time of re-enabling the disabling
function.
At the end of the forced-control position
function, the internal switching state will not be
changed. Thereafter, the output is again
enabled.
At the end of the forced-control position
function, the switching state is set to off. - The
output is re-enabled.
At the end of the forced-control position
function, the switching state is set to on. - The
output is re-enabled.
If a logic operation is parameterized, the state
is evaluated in the logic operation function in
such a way as if the state had been updated
via the "Switching" object (no evaluations of
time functions).